HomeMy WebLinkAbout174861_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
PROJECT ADDRESS:
PLAN CHECK ENGINEER:TEL:714FAX:714
647-5897
TYPE OF CONSTRUCTION:
OCCUPANCY CLASSIFICATION(S):
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
INITIAL REVIEW
EXPIRATION
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
3.
TEL:
FAX:
VALUATION:
EMAIL:
FLOOD ZONE:
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Please refer to drawings for additional plan check comments.Return marked up set of drawings with corrections.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700) - Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceCity records indicates the Type of building construction asType III-A. One HR construction is required. Please revisit all construction details for new walls, new ceilings assemblies and insure compliance with 1HR construction. Refer all fire rated assemblies to Table 7 and item number. Reference sheet A2.2, add Type “X” to 5/8” wall board in compliance with 1 HR for rating of walls. Please check other sheets to insure compliance.Indicate fire rated assembly based on Table 720 of CBC for 1 HR fire rated ceiling.Identify occupancy of each area on the drawings. Show required fire rated occupancy separation between various occupancies based on Table 504.4 of CBC.A-3 occupancy and B occupancy requires 1HR wall separation and 1HR fire rated door.
Reference sheet AO-1,
Please correct accessibility notes under parking data.
Revise accessible parking layout to match sheet AO-2.
Show location of 4” high curb.Provide dimensions and required clearances for reception deck, “PT” by kids club to insure wheelchair accessible area for employees. Show 34” maximum height on both sides of counters for clients as well as employees accessibility. Show location of accessible counter facing the client traffic area.Indicate the top of fixed or built-in counter, tables is between height of to be at 28” to 34” above the finish floor and knee clearance to be a minimum of 27” high, 30” wide, and 19” deep. CBC Sections 1122B of CBC.One of each type of station/counters shall be accessible.Reference sheet ID-4.0, ID4.0.2 and ID-4.3, show accessible counter of 34” max as marked on the drawings.Reference sheet ID-2.1, add 60” dimension (circle clearance) for sauna room.Show positive connection detail for lockers to wall on sheet ID-5.1.