PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10177571
PROJECT ADDRESS:
400 N Tustin Ave Unit# 301
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812FAX:714
647-5897
TYPE OF CONSTRUCTION:
II A, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/30/2012
INITIAL REVIEW
11/13/2012
EXPIRATION
4/28/2013
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Bert Elliot
3.
TEL:
(714)840-5488
FAX:
VALUATION:$91,365.00
EMAIL:
elliottarc@socal.rr.com
FLOOD ZONE:X-0602320277J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance
- Information Technology equipment rooms require a completed electrical plan check prior to issuance of the
building permit to ensure compliance with the 2010 California Electrical Code (CEC) Article 645, Electronic
Computer/Data Processing Equipment. CEC Article 645 may require fire-rated walls, floors, and ceilings for
the computer room(s). For additional information, contact Mr. Scott Davis, Electrical Plan Check at (714) 647-
5822.CBC Section 1129B.3. Revise the drawings to show disabled accessible parking space loading/unloading aisle on the PASSENGER SIDE.Please revise the wall legend on sheet G101, to match wall legend on sheet A101.Is there new I-hr fire rated all around stairways. Provide minimum 44” clearance (door landing) at the men’s bathroom. Provide minimum 12” clearance (door landing) at the men and women bathroom.