HomeMy WebLinkAbout184070_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10178150 Re-Check PROJECT ADDRESS: 2800 N Main St Unit# 854 PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: II B, SPK OCCUPANCY CLASSIFICATION(S): M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 2/14/2013 Main Mall, Yankee Candle Ti INITIAL REVIEW 3/14/2013 EXPIRATION 8/13/2013 RECHECKS: 1.4-4-2013 PROJECT APPLICANT CONTACT PERSON: 2. Sue Nieto 3. TEL: (626)200-3707 FAX: VALUATION:$57,620.00 EMAIL: FLOOD ZONE:X-0602320163J APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.(Please remove EMP sheets from this permit)This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceNote on the drawings that all interior floor finishes shall show compliance with CBC Section 804. Correct Type of construction to Type II-B and revise details to show compliance with Type II Non-combustible. Show Fire Retardant wood when used in Type II-B construction(sheet A-201B). Check door jam on sheet A-002 and specify fire retardant wood.Check sheet S-200 and specify fire retardant wood.Reference sheet A-005, show minimum of 10’.0” walk way for mall exit path.Provide dimensions for demo plan and new floor plan to show if there is any encroachment to mall exit path. Thank you for providing note on the drawings. Show actual dimension on the drawings for both demo plan and new floor plan. Reference sheet a-201A and A201B, Provide missing sheet A9/A201on each sets of drawings.Reference sheet A-101, Indicate height for racks (7E) show positive connection tom wall and submit structural calculations for design and justification when racks are 8’-0” or higher. Tenant improvements in the Main Place Mall shall show compliance with the following special provisions and CBC Section 402: - Note on drawings: Duct and smoke removal system modification is not allowed and shall be in compliance with the “Code Analysis and Fire Protection and Life Safety Concept.”