HomeMy WebLinkAbout185248_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10178512 PROJECT ADDRESS: 2800 N Main St Unit# 9087 PLAN CHECK ENGINEER: Ahangian, KathyTEL:714 647-5812FAX:714 647-5897 TYPE OF CONSTRUCTION: II B, SPK OCCUPANCY CLASSIFICATION(S): M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 4/11/2013 INITIAL REVIEW 4/24/2013 EXPIRATION 10/8/2013 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Eric Lopez 3. TEL: (562)696-1400 FAX: VALUATION:$13,000.00 EMAIL: eric@nbikiosks.com FLOOD ZONE:X-0602320163J APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceKiosk shall comply with CBC Section 402.10: - CBC Section 1604.9 and 1613. Kiosk anchorage to floor shall be by mechanical fasteners and resist all sliding and overturning forces induced by lateral forces. - Flame spread rating of kiosk construction shall comply with CBC Chapter 8. - Non-combustible materials are required for framework. CBC Sections 603 and 402.10, Item 1, for specific requirements. - Disabled access compliance is required. Refer to CBC Chapters 10 and 11B. - Floor surfaces shall be disabled accessible in accordance with CBC Section 1124B.Show the cash register is in compliance with disabled access.