HomeMy WebLinkAbout185831_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10178714
PROJECT ADDRESS:
2800 N Main St Unit# 308
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
II B, SPK
OCCUPANCY CLASSIFICATION(S):
M
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/9/2013
INITIAL REVIEW
5/15/2013
EXPIRATION
11/5/2013
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Chang Hak Park
3.
TEL:
(213)545-6595
FAX:
VALUATION:$10,770.00
EMAIL:
info@studiobatang.com
FLOOD ZONE:X-0602320163J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Refer to red marks on the drawings for additional plan check comments and return markup set of drawings to Building Dept. with 3 revised sets of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance All interior floor finishes shall show compliance with CBC Section 804. Correct Type of construction to Type II-B and revise details to show compliance with Type II Non-combustible. Show Fire Retardant wood when used in Type II-B construction. Note on the drawings that wood and wood veneer and such to be fire retardant.Show minimum of 20’.0” set back in front door (See red marks on the drawings) encroachment to mall is not permitted to reduce this required exit path distance.Note on the floor plan the use and occupant load of each room and/or area based on CBC Section 1004 and Table 1004.1.1.Refer to Table 1015.1 for spaces with one means of egress based on maximum occupant load. Refer to Table 1019.1 for buildings with one exit and maximum travel distance. Show compliance on the drawings. (When applicable) CBC Section 1122B.1. Where a single counter contains more than one transaction station, such as (but not limited to) a bank counter with multiple teller windows or a retail sales counter with multiple cash register stations, at least 5 percent, but never less than one, of each type of station shall be located at a section of counter that is at least 36” long and no more than 28 to 34” high.It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. This project is reviewed for compliance with State Accessibility Standards.Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use.
Note on drawings:
- Provide mechanical ventilation for each area/room in accordance with the 2007 California Mechanical Code.Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use.
Note on drawings:
- CBC Section 1205.3, Artificial light. Artificial light shall be provided that is adequate to provide an average
illumination of 10’candles (107 lux) over the area of the room at a height of 30”above the floor level.Tenant improvements in the Main Place Mall shall show compliance with the following special provisions and CBC Section 402:
- CBC Section 106.3. Tenant improvements at 2800 North Main, Main Place Mall, shall show compliance with
“Code Analysis and Fire Protection and Life Safety Concept” prepared by Code Consultants Incorporated,
dated “Revised February 18, 1986, and February 22, 1990 (1991 Mall Expansion).”
- Note on drawings: Duct and smoke removal system modification is not allowed and shall be in compliance
with the “Code Analysis and Fire Protection and Life Safety Concept.”Plans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Section 106.1.1 and CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana.Reference sheet A-05, removal of fire rating of existing column to be replaced to maintain 2 hour fire rating of existing column. Specify ICC approval number for spry type fire rating and indicate thickness of applied fire rated spray. Refer to Table 7 of CBC and provide a copy description of proposed fire rating on the drawings to insure existing fire rating is maintained.CBC Section 402.12, Security grilles and doors. Horizontal sliding or vertical security grilles or doors, which are part of a required means of egress, shall conform to the following: (If applicable)
- They must remain secured in the full open position during the period of occupancy by the general public.
- Doors or grilles shall not be brought to the closed position when there are more than 10 persons occupying
spaces served by a single exit or 50 persons occupying spaces served by more than one exit.
- The doors or grilles shall be openable from within without the use of any special knowledge or effort when the
space is occupied.
- When two or more exits are required, not more than one half of the exits may be equipped with horizontal
sliding or vertical rolling grilles or doors.
- Note on Drawings: Post a legible sign at security grill/door closing controls stating “Security grill/door shall
remain secured in the full open position during the period of occupancy by the general public.”Note On Drawings: (Santa Ana Police Department Requirement)SANTA ANA POLICE DEPARTMENT REQUIREMENTS FOR MAINPLACE OVERHEAD/ROLLING GRILLESECURITYORDINANCE REQUIREMENTSTUBES ARE TO BE “DOUBLE TUBED” (NO MORE THAN ½” APART) AND CONSTRUCTED OF ½” STEEL OR BE STEEL REINFORCED TUBES WITHIN 40” OF ALL LOCKING HARDWARE. PERFORATED SLATS CAN BE USED INSTEAD OF THE AFOREMENTIONED AS LONG AS THEY ARE CONSTRUCTED OF MINIMUM 20 GA STEEL.LOCKING MECHANISM TO BE STEEL SLIDEBOLTS BOTH SIDES OF DOOR. SLIDEBOLTS TO EMBED AMINIMUM OF ½” INTO THE RECEIVING GUIDE.CURTAIN GRILLES ARE NOT TO BE UTILIZED.FIRE DEPARTMENT REQUIRED EMERGENCY RELEASE MUST BE LOCATED NO MORE THAN 40” FROM THE EXTERIOR SIDE OF THE GRILLE.THE LOCKING MECHANISM’S INTERIOR THUMBTURN MUST BE SHIELDED BY AN INTERIOR HOOD TO PREVENT ITS MANIPULATION FROM THE EXTERIOR SIDE OF THE GRILLE.Provide on the drawings a complete window schedule showing:
- Window sizes
- Type and thickness of glazing (type of safety glazing for hazardous locations noted under CBC Section 2406.3Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3.Note type of safety glazing complying with CBC Section 2406 for glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24” arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60” above the walking surface.Glass shall be firmly supported on all four edges. Show on the drawings how compliance shall be made with CBC Section 2404. For glass not firmly supported on all four edges, design shall be submitted to the building official for approval.CBC Section 1006, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.Tactile exit signs shall be required at the following locations:
- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”
- Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure, or an exit
passageway, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”
- Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual
exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”For the purpose of Section 1011.3, the term “tactile exit signs” shall mean those required signs that comply with Section 1117B.5.1, Item 1.Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636.Note ICC Research Report Number on the drawings for the suspended ceiling system in lieu of providing structural calculations for justification. (ICC Report Number 1308).Incorporate results of structural calculations into drawings prior to resubmit. Structural drawings to be signed by engineer of record ( Mr.Junta Park)Refer to red marks on the drawings for additional plan check comments and return markup set of drawings to Building Dept. with 3 revised sets of drawings.