HomeMy WebLinkAbout186136_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10178820
PROJECT ADDRESS:
3402 W MacArthur Blvd Unit# D
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812FAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
F-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/22/2013
INITIAL REVIEW
6/1/2013
EXPIRATION
11/18/2013
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Gilbert Nguyen
3.
TEL:
(714)383-1654
FAX:
VALUATION:$18,000.00
EMAIL:
gilbertnguyen2007@yahoo.com
FLOOD ZONE:X-0602320258J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.All persons preparing plans, specifications, and instruments of service for others shall sign those plans, specifications and other instruments of service for others shall sign those plans, specifications and other instruments of service and all contracts therefore. This requirement applies to both exempt and non-exempt projects. Business and Professions Code Chapter 3, Division 3, Section 5536.1(a).Include address and telephone number of the responsible designer, and date of signing of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceShow on the plans:
- Occupancy Classification(s)
- Type of ConstructionProvide typical section view detail of all new partitions and ceilings showing:
- Size, spacing, and material of framing members
- Note gauge and ICC Research Report number and installation/construction requirements for metal framing
members.
- Method of attaching framing to the building structure. Compliance shall be shown with CBC Section 1607.13
for lateral support of the walls. Do not support top of walls to suspended ceiling system unless calculations
and drawing prepared by a registered engineer are submitted for review. Submit structural engineering
calculations for walls in rooms with a floor to building structure above height greater than 14’.
- Heights of partition, suspended ceiling, structure above.The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. CBC Section 1126A.3.2.Provide specifications for doors hardware (i.e., lever type, push-pull panic, etc) to comply with disabled access requirements. CBC Section 1133B.2.5.2.CBC Section 1133B.2.5, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.Exit illumination and exit sign requirements in accordance with CBC Section 1011 shall be shown on the drawings. Be specific as to the type of exit signs to be installed.If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 1133B.8.5.
Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 1133B.8.5.Disabled accessible parking spaces should be sized as follows:
- CBC Section 1129B.3, Item 1. Where single spaces are provided, they shall be a 9’ wide parking area with
an outlined 5’ wide (8’ wide for van accessible space) loading and unloading aisle ON THE PASSENGER SIDE
OF THE VEHICLE. The minimum length of each parking space shall be 18’. The loading and unloading access
aisles shall be marked by a border painted blue. Within the blue border, hatched lines a maximum of 36” on
center, shall be painted a color contrasted with the parking surface, preferably blue or white. Parking access
aisles shall be part of an accessible route of travel (complying with Section 1114B.1.2) to the building or facility
entrance. Parked vehicle overhangs shall not reduce the clear width of an accessible route. The words NO
PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be
painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials.
See Figure 11B-18A.
- CBC Section 1129B.3, Item 1. When more than one space is provided, two 9’ wide parking areas may be
outlined on each side of a 5’ wide (8’ wide for van accessible space(s)) loading and unloading aisle. The
minimum length of each parking space shall be 18’. The loading and unloading access aisles shall be marked
by a border painted blue. Within the blue border, hatched lines a maximum of 36” on center, shall be painted
a color contrasted with the parking surface, preferably blue or white. See Figure 11B-18A. Parking access
aisles shall be part of an accessible route of travel (complying with Section 1114B.1.2) to the building or facility
entrance. Parked vehicle overhangs shall not reduce the clear width of an accessible route. The words NO
PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be
painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials.
See Figure 11B-18A.CBC Section 1607.7. Provide complete grab bar details on the drawings showing compliance with CBC Section 1115B.8 including structural strength to support a 250 pound point load.Provide detail to infill the existing door.