Loading...
HomeMy WebLinkAbout186970_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10179093 PROJECT ADDRESS: 3030 S Orange Ave PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/24/2013 INITIAL REVIEW 7/3/2013 EXPIRATION 12/21/2013 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Steve Zamolo 3. TEL: (714)641-8813 FAX: VALUATION:$4,000.00 EMAIL: greg@uremet.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3corrected sets of plans.(When needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please return marked up set of drawings with corrections.7. All drawings shall be signed by the person who prepared these plans and specifications.Include address and telephone number of the responsible designer, and date of signing of drawings.Please refer to red marks on the drawings for additional plan check comments. Revise drawings to show compliance.(Remove electrical drawings) This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide a wall legend indicating whether the wall is:- Existing, new, or to be removed - A fire-resistive assembly.Note on the floor plan the use and occupant load of each room and/or area based on CBC Section 1004 and Table 1004.1.1. Revise “RTO” room based on Table 1004.1.1 of CBC.Note on the drawings if spray booth is new or existing. New spray booth requires OCFA approval.Provide natural ventilation per Section 1203.4 and natural or artificial lighting per section 1205 of CBC. In lieu of natural ventilation provide mechanical ventilation per California Mechanical code.Provide typical full height cross sections through new partitions showing: - Size, spacing, and material of framing members. 2x8 studs are required for 20 span including fire blocking - Fire-blocks in combustible construction in accordance with CBC Section 717. Show location(s) and provide typical construction details.Exit illumination and exit sign requirements in accordance with CBC Section 1011and CBC Section 1006, requires means of egress from all occupied parts of the building to be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.Drawings submitted to the Building Division for review shall provide the following drawings/information to insure compliance with CBC Section 1134B/Chapter 11B: - An accessible entrance - An accessible route to the altered area - Accessible restrooms - Accessible telephone (if any) - Accessible drinking fountains, and - Parking, signage and alarmsValuation of proposed project is calculated as $4000. A minimum of 20% of valuation of construction is required to be spent towards providing disabled access in the priority order noted in the immediate previous item as noted in CBC Section 1134B. Revise the drawings to show compliance. Show both existing elements and how they will be upgraded to current standards.If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 1133B.8.5. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 1133B.8.5.Provide missing site plan including accessibility compliance.