HomeMy WebLinkAbout187899_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10179355
PROJECT ADDRESS:
2800 N Main St Unit# 236
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812FAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
M
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/1/2013
INITIAL REVIEW
8/12/2013
EXPIRATION
1/28/2014
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Tasia Kallies
3.
TEL:
(312)260-7090
FAX:
VALUATION:$175,000.00
EMAIL:
TKallies@Burnhamnationwide.com
FLOOD ZONE:X-0602320163J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide typical section view detail of all new partitions and ceilings showing:
- Size, spacing, and material of framing members
- Note gauge and ICC Research Report number and installation/construction requirements for metal framing
members.
- Heights of partition, suspended ceiling, structure above.Complete all soffit and furred out wall details. Provide complete detailing, including number, type, location of fasteners and how attachment is made to the building structure. Show compliance with CBC Section 803.Provide complete framing detail for gypsum ceiling.Provide on the drawings interior wall and ceiling finish schedule showing compliance with CBC Section 803 and CBC Table 803.5.Provide complying exiting plan for the “reminder, adjacent unit ” area. Note the use of adjacent units.CBC Section 1133B.2.5, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.Tactile exit signs shall be required at the following locations:
- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”
- Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be
identified by a tactile exit sign with the following words as appropriate:“EXIT STAIR DOWN”“EXIT RAMP DOWN”“EXIT STAIR UP”“EXIT RAMP UP”
- Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure, or an exit
passageway, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”
- Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual
exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”
- Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.”CBC Section 1115B.4.3 Item 4. Note on the drawings hot water and drain pipes under lavatory shall be insulated.Provide 16”- 18” clearance from the center of toilet to the wall.Show 7”-9” clearance from the toilet to the bathroom tissue dispenser.Show cash register is in compliance with disabled access.Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636. (OR SEE COMMENT #17- 18)The reflected ceiling plan and details must show compliance with CBC Sections 711.3.1, 803, 1613, and 1705 (special inspection) for suspended ceiling systems.Note ICC Research Report Number on the drawings for the suspended ceiling system. (ICC Report Number 1308)Tenant improvements in the Main Place Mall shall show compliance with the following special provisions and CBC Section 402:
- CBC Section 106.3. Tenant improvements at 2800 North Main, Main Place Mall, shall show compliance with
“Code Analysis and Fire Protection and Life Safety Concept” prepared by Code Consultants Incorporated,
dated “Revised February 18, 1986, and February 22, 1990 (1991 Mall Expansion).”
- Note on drawings: Duct and smoke removal system modification is not allowed and shall be in compliance
with the “Code Analysis and Fire Protection and Life Safety Concept.”CBC Section 402.12, Security grilles and doors. Horizontal sliding or vertical security grilles or doors, which are part of a required means of egress, shall conform to the following:
- They must remain secured in the full open position during the period of occupancy by the general public.
- Doors or grilles shall not be brought to the closed position when there are more than 10 persons occupying
spaces served by a single exit or 50 persons occupying spaces served by more than one exit.
- The doors or grilles shall be openable from within without the use of any special knowledge or effort when the
space is occupied.
- When two or more exits are required, not more than one half of the exits may be equipped with horizontal
sliding or vertical rolling grilles or doors.
- Note on Drawings: Post a legible sign at security grill/door closing controls stating “Security grill/door shall
remain secured in the full open position during the period of occupancy by the general public.”CBC Section 402.15.5.2, Plastic panel and plastic signs. Within every story or level and from side wall to side wall or each tenant space or mall, plastic panels and plastic signs shall be limited as follows:
- Plastics, other than foam plastics, shall comply with CBC Section 402.15.4.
- Foam plastics shall have a maximum heat-release rate of 150 kilowatts when tested in accordance with
approved recognized standards (see CBC Section 402.15.5) and shall have the following physical
characteristics:
- They shall be located a minimum distance of 18” from adjacent tenants.