Loading...
HomeMy WebLinkAbout187936_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10179365 PROJECT ADDRESS: 1900 E Fourth St PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 8/5/2013 INITIAL REVIEW 8/9/2013 EXPIRATION 2/1/2014 RECHECKS: 1. 9-18-2013 PROJECT APPLICANT CONTACT PERSON: 2. Michael Morrell 3. TEL: (949)955-1919 FAX: VALUATION:$65,000.00 EMAIL: Michael.Morrell@lionakis.com FLOOD ZONE:X-0602320277J APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTSThe applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Public Works Agency approval (647-5039) - Police Department approval on the corrected/final set of drawings (647-5840) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuancePlease see below commentsas part of recheck review of drawings and calculations. Refer to plan check report dated 8-9-2013.Submit complete structural calculations for design and justification of each and ALL existing floor and roof members subject to additional new and existing equipment loads. (5 1/4x 24, 4x14, 5 1/8 x 24) Check location of exiting column and show correct location.Submit complete truss analysis including top and bottom cord analysis when subject to new screws, (spacing not specified) for additional plywood. Calculations to consider new plywood and equipment loads for trusses modification.Also structural calculations to consider dead loads of existing and new equipment. Provide complete detail/s including attachment method based on finding and justification of structural calculations. Submit dimensioned floor framing plan.Provide reference from each detail on sheet AE5-01 to roof and floor framing sheet. Drawings are missing floor framing plan to show cross reference from sheet AE5-01, details 1 and 4.Structural drawings must be signed by structural engineer. And incorporate the results of structural calculations into drawings prior to re-submittal.CBC Section A106.1. Calculations must be presented in a clear, legible, and organized manner conducive for structural plan review. A table of contents must be provided and pages must be numbered for referencing purposes. Resubmit revised calculations showing compliance.CBC Section A106.1. A key plan must be provided for the structural members designed on all pages of calculations so that the calculations and plans may be correlated.CBC Section A106.1. A correlated grid system must be provided on the structural calculations and drawings to facilitate plan review process.CBC Section A106.1. Details must be provided on the plans for items designed in the calculations.