HomeMy WebLinkAbout190400_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10180130
PROJECT ADDRESS:
2040 E Dyer Rd
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
11/14/2013
Access control doors
INITIAL REVIEW
2/10/2014
EXPIRATION
5/13/2014
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Alex Paik
3.
TEL:
(714)816-1323
FAX:
VALUATION:$90,000.00
EMAIL:
alex.paik@siemens.com
FLOOD ZONE:X-0602320278J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit 3corrected sets of plans.(when needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831 for an appointment.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceThe drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2010 California Building Standards Code with local amendments.Remove non-applicable drawings. Building permit is not an electrical permit. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.Provide complete floor plan and show location of all doors and clearly identify doors to be equipped with access control. Identify location of all rated or non-rated corridors on the drawings.Provide elevation to show maximum height of 54” for location of card readers on the drawings to insure accessibility compliance.
Please refer to attached Section1008.1.3.4, CBC (Access-control egress doors) and revise drawings to show compliance with all applicable items.
A letter of certification and documentation from the door manufacture and frame manufacture for all fire-rated door assemblies that requires drilling for modification, demonstrating retention of fire-rating is required. Attach certification from a nationally recognized testing laboratory that shows drilling criteria on the drawings.
Note on the drawings that all exit doors to have electronic device(s) to be operable from inside without special knowledge or key.
Additional plan check comments may apply.