HomeMy WebLinkAbout194301_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10181339 PROJECT ADDRESS: 1431 S Village Way Unit# A PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/13/2014 INITIAL REVIEW 5/15/2014 EXPIRATION 11/9/2014 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Brad Kelly 3. TEL: (949)533-5722 FAX: VALUATION:$50,260.00 EMAIL: Brad@Makenaprop.com FLOOD ZONE:X-0602320277J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3corrected sets of plans. Please refer to mark up set of drawings for additional plan check comments. Return marked up set of drawings with corrections.(when needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuancePlease correct Type of construction from Type III-B to Type V-B per City records. Reference each fire-resistive assembly to a CBC Chapter 7, Table and Item number: Provide a copy of selected assembly on the drawings. Show 1hour wall separation between units. Please refer to red marks on the drawings for additional plan check comments. Correct wall legend.Provide ICC approved span Table for 20 gage wall for span of 20’.00 on the drawings.Provide enlarged area of parking and correct location of accessible parking and landing.Show compliant maximum 75’.0” Path of travel distance from each area remote area toward exit doors until the exit path can be achieved by going in two different routes of travel toward exit door. See Table 1015.1 of CBC. Table 1015.1 Spaces with One Means of Egress: OccupancyMaximum Occupant Load A, B, M49 11. Also show maximum of 250’.0” of exit travel starting at where there is path of travel option in eitherDirection toward two exit doors (Starting where 75’.0” travel distance was left off). See Table 1016.1 of CBC. Table 1016.1 Exit Access Travel Distance: OCCUPANCY WITHOUT SPRINKLERWITH SPRINKLER SYSTEM (feet)SYSTEM (feet) A, M 200250b B 200300cAll doors require a level floor landing on each side in accordance with CBC Sections 1008.1.4, 1008.1.5, 1008.1.6, and 1133B.2.4 and CBC Figures 11B-26A and 11B-26B. Provide typical door threshold details and details of change in floor covering material.Complete all soffit and furred out wall details. Provide complete detailing, including number, type, location of fasteners and how attachment is made to the building structure. Show compliance with CBC Section 803. Provide structural collations for design and justification.Refer to the attached entrance/door handout and show compliance with following items The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. Please see floor plan. All building entrances that are accessible to and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.Hand-activated door opening hardware shall be centered between 30” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Locked exit doors shall operate as above in egress direction. Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.If carpet or carpet tile is used on a ground or floor surface, then it shall be securely attached; have a firm cushion, pad or backing or no cushion or pad; and have a level loop, textured loop; level-cut pile, or level-cut/uncut pile texture. The maximum pile height shall be ½”. Exposed edges of carpet shall be fastened to floor surfaces and have trim along the entire length of the exposed edge. Carpet edge trim shall comply with the requirements for changes in level.All occupied parts of the building are provided with at least 1’ candle of light at floor level. Show compliance on the drawings. Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT” with Tactile exit signs.It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. If applicable please remove notes referring to ADA compliance from drawings. This project is reviewed for compliance with State Accessibility Standards.Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC 11-B, Division 2. - An accessible entrance - An accessible route to the altered area - Accessible restrooms - Accessible telephone (if any) - Accessible drinking fountains, and - Parking, signage and alarms Provide truncate domes to cove the accessible parking stall landing. If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements (at zero curb) between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 1133B.8.5. Also please clarify path of travel from parking to building entrances on the site plan Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 1133B.8.5. (Show location of all counters on the drawings) Indicate the top of fixed or built-in counter, tables is between height of to be at 28” to 34” above the finish floor and knee clearance to be a minimum of 27” high, 30” wide, and 19” deep. CBC Sections 1122B of CBC.One of each type of station/counters shall be accessible.Provide enlarged floor plan of sanitary rooms. Please refer to attached accessibility handouts and revise drawings to show compliance.CBC Section 1115B.4.3 Item 4. Note on the drawings hot water and drain pipes under lavatory shall be insulated.Show location of drinking fountains on the floor plan, drinking fountains serving the area of new work shall be accessible (High and low). Please refer to Table 422.1 of CPC. 23. Identify Storage room designation. Provide a key or legend for clarification for all and each item as called out on the drawings.Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use. Note on drawings:- Provide mechanical ventilation for each area/room in accordance with the 2013 California Mechanical Code.Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Note on drawings:- CBC Section 1205.3, Artificial light. Artificial light shall be provided that is adequate to provide an average illumination of 10’candles (107 lux) over the area of the room at a height of 30”above the floor level. Please complete attached accessibility form and return with correct drawings. Refer to red marks on the drawings for additional plan check comments. Return markup set of drawings.