HomeMy WebLinkAbout194626_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10181456
PROJECT ADDRESS:
2800 N Main St Unit# 196B
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
II B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/28/2014
INITIAL REVIEW
7/2/2014
EXPIRATION
11/24/2014
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Denise Torres
3.
TEL:
(310)320-6285
FAX:
(310)320-8073
VALUATION:$85,910.00
EMAIL:
denise.torres@tarci.com
FLOOD ZONE:X-0602320163J
APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3 corrected sets of plans.(When meeting is needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information. Please remove electrical, mechanical and plumbing sheets.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings (647-5839 or 647-5700)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- County of Orange Health Department approval on the corrected/final set of drawings (667- 3600)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide roof plan to show location of proposed equipment and submit structural calculations for design and justification.Reference sheet 1.0 and sheet 1.1, provide legible site plan. Revise location of accessible parking so that wheel chair does not wheel behind any parked cars.Refer sheet 2.1, Identify location of indoor and outdoor dining area on the floor plan. Additional plan check comments may apply.Reference sheet 3, revise door location so it does not block the exit way for any door.Reference sheet 3.1 show tempered glass for double entry door.Reference sheet 3.23, provide accessible seating area for indoor dining area. And revise location of exit doors.Reference sheet 6.3 and 6.7, show non-combustible constriction for Type II-B construction. Provide on the drawings a complete door schedule, showing: - Hardware complying with exiting and disabled accessibility requirements (CBC Sections 1008.1.8 andShow/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use.
Note on drawings: - Provide mechanical ventilation for each area/room in accordance with the 2013California Mechanical Code. Note on drawings: Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use.Revise all details to show non-combustible members and fire retardant plywood for compliance with Type II-B building. Label composite floor plan as 1st level to clarify location of proposed project.Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3.Tenant improvements in the Main Place Mall shall show compliance with the following special provisions and CBC Section 402:
- CBC Section 106.3. Tenant improvements at 2800 North Main, Main Place Mall, shall show compliance with
“Code Analysis and Fire Protection and Life Safety Concept” prepared by Code Consultants Incorporated,
dated “Revised February 18, 1986, and February 22, 1990 (1991 Mall Expansion).”
- Note on drawings: Duct and smoke removal system modification is not allowed and shall be in compliance
with the “Code Analysis and Fire Protection and Life Safety Concept.”
- Main Place Mall, other than anchor stores, is of Type IIB fire-sprinklered construction. In accordance with
CBC Section 603.1, walls and permanent partitions shall be of noncombustible construction, except that
permanent non-bearing partitions may use fire-retardant treated wood (CBC 202) within the assembly.
- CBC Sections 402.7.2 and 708. Each tenant space shall be separated from other tenant spaces by a wall
having a fire-resistive rating of not less than one hour. The separation wall shall extend from the floor to the
underside of the ceiling above.CBC Section 402.12, Security grilles and doors. Horizontal sliding or vertical security grilles or doors, which are part of a required means of egress, shall conform to the following:
- They must remain secured in the full open position during the period of occupancy by the general public.
- Doors or grilles shall not be brought to the closed position when there are more than 10 persons occupying
spaces served by a single exit or 50 persons occupying spaces served by more than one exit.
- The doors or grilles shall be openable from within without the use of any special knowledge or effort when the
space is occupied.
- When two or more exits are required, not more than one half of the exits may be equipped with horizontal
sliding or vertical rolling grilles or doors.
- Note on Drawings: Post a legible sign at security grill/door closing controls stating “Security grill/door shall
remain secured in the full open position during the period of occupancy by the general public.”Drawings submitted to the Building Division for review shall provide the following information to insure compliance with Chapter 11B division 2:
- An accessible entrance
- An accessible route to the altered area
- Accessible restrooms
- Accessible telephone (if any)
- Accessible drinking fountains, and
- Parking, signage and alarmsCheck Stands CBC Table 11B-2. Check stands must be accessible to both employees and customers. Please refer to plan check comment below: ( Please see comment 23 below)
NUMBER OF REGULAR NUMBER TO BE
CHECKSTANDS ACCESSIBLE
1 to 41All dining, banquet, and bar facilities shall be made accessible to persons with disabilities. At least 5%, but not less than one of the seating spaces in each functional area to be accessible as follows:
- Provide 60” length counter. -Provide a minimum 30” x 48” wheelchair clear floor space.
- Provide knee space at tables at least 27” high, 30” wide and 19” deep.
- Provide height of tables between 28” – 34” from the floor ground.
- Provide access to accessible seating space(s) by aisles with a minimum of 60”” in width.- Show location of accessible seating with signage on the drawings for each area and identify location of indoor and outdoor dining area. Provide parking data on the site plan showing the total number of parking spaces provided the number of disabled accessible spaces and the number of van accessible spaces, showing compliance with CBC Section 11B-501 and CBC Table 11B-208.2.Parking spaces must be located so that the disabled are not compelled to walk or wheel behind parked cars other than their own. Revise existing parking layout to show disabled parking stall is located where not walking behind any parking stalls. Revise drawings.Provide parking data on the site plan showing the total number of parking spaces provided, the number of disabled accessible spaces and the number of van accessible spaces. One in every eight accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible. The words NO PARKING shall be painted on the ground within each eight’ loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials.
Reference sheet A101, provide truncate domes to cove the accessible parking stall landing. If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements (Zero curb) between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide. Show location of landscaping and all existing 4”/6” curb on the drawings.
Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 1133B.8.5. Separate, disabled accessible, sanitary facilities shall be provided for each gender when required by Section 422.2 and Table 422.1 of CPC. The proposed restaurant was not part of original calculations for required number of toilet rooms that are located on the 2nd floor food court. The existing area of remodel was M occupancy (Retail store). Please note foot note #3 for additional women’s toilet stall.Show location of accessible high and low drinking fountain per Table 422.1 of CPC for this occupancy.The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. Show 18” clearance for door number to new toilet room. See drawings for locationComplete the attached Disabled Accessibility Documentation Form.