Loading...
HomeMy WebLinkAbout194522_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10181419 PROJECT ADDRESS: 1713 W Wilshire Ave PLAN CHECK ENGINEER: Ahangian, KathyTEL:714 647-5812FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/21/2014 INITIAL REVIEW 5/27/2014 EXPIRATION 11/17/2014 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Arturo Garcia 3. TEL: (949)500-6272 FAX: (714)241-0534 VALUATION: $21,520.00 EMAIL: newportdraft@sbcglobal.net FLOOD ZONE: X-0602320257J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2013 California Residential Code (CRC); 2013 California Building Code (CBC); CMC = 2013 California Mechanical Code; CPC = 2013 California Plumbing Code; CEC = 2013 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2010 California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review. Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper. Provide building information on plans: - Occupancy type: R3 / U - Construction type: Type V – B Provide a statement on the title sheet of the plans that this project shall comply with following codes: - 2013 California Residential Code (CRC) - 2013 California Building Code (CBC) - 2013 California Electrical Code (CEC) - 2013 California Mechanical Code (CMC) - 2013 California Plumbing Code (CPC) - 2013 California Green Building Standards Code (CGBS) or CALGreen - 2010 California Energy Code (CEnC) - City of Santa Ana Municipal CodeShow location of heating equipment on the plans. (CRC R303.8)Doors between the garage and private residence shall be self-closing and self-latching. (CRC R302.5.1) Provide a complete full-height section and details of stairway showing: (CRC R311.7) - Maximum rise of 7¾ inches and minimum run (tread) of 10 inches. - Minimum width of 36 inches. - Framing (stringer, landing, etc.) size, bracing, connections, footings. - Stairways positively anchored to the primary structure without using toe nails or nails subject to withdrawal. Callout attics vent locations, sizes and types on plans. Provide attic ventilation calculation to show minimum ventilation is provided. (CRC R806.2) Add note on foundation plan: All hold downs must be tied in place prior to foundation inspection. 3”x3”x.229” steel plate washers are required on all anchor bolts in a braced wall line. (CRC R403.1.6.1)For plywood floor diaphragm specify thickness, grade, T&G edges, panel span rating, nailing schedule and panel layout pattern. (CBC 2305, T2305.2.3, 2306.3, T2306.3.1, and T2306.3.2) Provide a minimum of two No. 4 bars at top and at bottom of continuous footing. Provide detail of post support with positive connections. (1203.3) Show minimum 18-inch underfloor clearance from grade to bottom of floor joists and minimum 12-inch clearance to bottom of girders. (2304.11.2.1) Detail how the interior shear walls are connected to the roof/floor diaphragm(s). (1603)All wood framing members that rest on concrete or masonry exterior foundation walls and are less than 8” to the exposed ground shall be pressure treated or naturally durable to decay. (CRC R317.1 (2)) For plywood roof and floor diaphragm specify thickness, grade, T&G edges, panel span rating, nailing schedule and required blocking and panel layout pattern. Provide details for retrofit shear and tension anchor bolts on plans. Provide calculations as needed. Call out anchor bolt size and spacing on foundation plan. Provide 1/2" diameter embedded 7" minimum at 6' o.c. maximum spacing (4' o.c. for 2 stories). CRC R403.1.6 The residence shall conform to the State Energy Conservation Standards. Submit forms and calculations for review and blueprint the final forms on the plans. - Signed Energy Efficiency Documents must be printed on the plans. - Also, submit 2 copies of signed Energy Efficiency calculations. - The corrected/final drawings shall have the required energy efficiency compliance documentation with completed signature blocks filed on the plans. - The energy plan check consultant must also complete the attached “Energy Conservation Plan Check Consultant Qualification Statement”. Landing at door shall have a length measured in direction of travel of not less than 36 inches. Specify that the maximum slope of any landing shall not exceed 1/4 inch per foot. Provide complete roof framing to include ceiling joists and roof rafters at the new porch. On elevation location of 2x8 ridge board doesn’t match roof framing plan. Please clarify the head clearance at the patio cover, 3:12 slope couldn’t provide 7feet head room. Provide shear wall on left side of the addition.