HomeMy WebLinkAbout195639_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10181762
PROJECT ADDRESS:
1900 E Fourth St
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
6/26/2014
SPK to be verified
INITIAL REVIEW
7/1/2014
EXPIRATION
12/23/2014
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Audric Menu
3.
TEL:
(949)955-1919
FAX:
VALUATION:$290,000.00
EMAIL:
FLOOD ZONE:X-0602320277J
APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Please refer to drawings for additional plan check comments.Return marked up set of drawings with corrections.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings (OCFA, 714-573-6108)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceReference sheet G0-01, Correct Type of construction to Type V-B based on 2013 CBC.Reference sheet A1-12, note on the drawings if existing corridor area is one hour fire rated. Or if corridor area to be non-rated and equipped with sprinklered system.Where corridor walls are required to be one-hour fire-resistive construction by Section 1017, windows shall be protected by fixed glazing listed and labeled for a fire-protection rating of at least three-fourths hour. The total area of windows in any portion of an interior corridor shall not exceed 25 percent of the area of the corridor wall of the room which it is separating from the corridor.When corridor walls are required to be of one-hour fire-resistive construction by Section 1017, every interior door opening shall be protected by a tight-fitting smoke-and-draft-control assembly having a fire-protection rating of not less than 20 minutes. Viewport in 20-minute rated door limited to 1” in diameter. Said doors shall not have louvers. Reference sheet A1-12, remove all casework from corridor area and remove incorrect cross reference to sheet A2-15.
- Cabinets such as recessed electrical panels, fire hose cabinets, and recess fire extinguisher cabinets
constructed of steel are permitted, provided that the openings in the fire rated corridor are sealed with
approved sealant material to prevent the passages of smoke.
- Other cabinets should be installed or recessed so that there is no reduction in the fire rating of the wall, or
opening which would allow smoke to pass. This would mean that the cabinet must be surrounded with
material which provides the equivalent of one-hour fire resistance.Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use.
Note on drawings:- Provide mechanical ventilation for each area/room in accordance with the 2013 California Mechanical Code. Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use. Note on drawings:Artificial light. Artificial light shall be provided that is adequate to provide an average
illumination of 10’candles (107 lux) over the area of the room at a height of 30”above the floor level.Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636. In-lieu of providing structural calculation for design of suspended ceiling, Note ICC Research Report Number on the drawings for the suspended ceiling system. (ICC Report Number 1308 or other approved products by ICC)Reference sheet A2-13, Sheet E1.1 and E1.2, Note type of safety glazing complying with CBC Section 2406 for glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24” arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60” above the walking surface. Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3Reference sheet A5-04, detail 5, Note on the drawings hot water and drain pipes under lavatory shall be insulated.Drawings submitted to the Building Division for review shall provide the following information ( drawing and details are enquired to examine all of the following items for compliance) to insure compliance with CBC Section 11B- Division 2:
- An accessible entrance
- An accessible route to the altered area
- Accessible restrooms
- Accessible telephone (if any)
- Accessible drinking fountains, and
- Parking, signage and alarms(FYI) It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. If applicable please remove notes referring to ADA compliance from drawings. This project is reviewed for compliance with State Accessibility Standards (T-24)Provide parking data on the site plan showing the total number of parking spaces provided the number of disabled accessible spaces and the number of van accessible spaces, showing compliance with CBC Section 11B-501and CBC Table 11B-208.2Reference sheet AS1-01, if a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide. Provide enlarge site plan to show location of existing curbs and zero curb and all landscaping/planter area clearly show location of truncated dome where applicable.
Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products and directional surfaces shall be installed in accordance with CBC Section 11B-705.1At every entrance and at every major junction along or leading to an accessible route of travel, there shall be a sign displaying the international symbol of accessibility. Signs shall indicate the direction to accessible building entrances and facilities. Show accessible path from public bus stop to main entrance of existing building.Refer to the attached handout for Exterior Routes of Travel. Revise drawings to show compliance. Please revise code Sections of handout to new code Sections of 2013 CBC when coping into drawings.Provide drawings to insure compliance for all doors that are part of this permit and path of travel including exiting entrance door/s:The following information for all doors requires a level floor landing on each side. Provide typical door threshold details and details of change in floor covering material.The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. Provide specifications for doors hardware (i.e., lever type, push-pull panic, etc.) to comply with disabled access requirements. Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds. All building entrances that are accessible to and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Refer to the attached entrance/door handout. Revise the drawings to show compliance.Indicate the top of fixed or built-in counter, tables is between height of to be at 28” to 34” above the finish floor and knee clearance to be a minimum of 27” high, 30” wide, and 19” deep.All counter area to be accessible to customers and employs.
- Provide a minimum 30” x 48” wheelchair clear floor space.
- Provide knee space at tables at least 27” high, 30” wide and 19” deep.
- Provide height of tables between 28” – 34” from the floor ground.
- Provide access to accessible seating space(s) by aisles with a minimum of 36” in width.