Loading...
HomeMy WebLinkAbout193191_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10280981 PROJECT ADDRESS: 1228 N Broadway PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 8/18/2014 INITIAL REVIEW 11/12/2014 EXPIRATION 2/14/2015 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. John Clabaugh 3. TEL: (949)466-9933 FAX: VALUATION:$5,000.00 EMAIL: Johnclabaugh@jrcinc.net FLOOD ZONE:X-0602320163J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2013 California Building Code (CBC); MC = 2013 California Mechanical Code; PC = 2013 California Plumbing Code; EC = 2013 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.Include address and telephone number of the responsible designer and date of signing of drawings. This review does not include electrical work. Separate plan, application, fee, plan check, and permit is required for electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. As required in section 420.6.2.2 of California Building Code, provide Carbon monoxide alarms for this alternation. The description of work for this permit in our system says: “Legalize replacement of front stair balcony including landing (floor, guardrails & handrails); replace rear balcony (footboards, handrails, spindles). The drawing only shows the replacement of rear balcony. Provide the rest of items to be “Legalized” per description above. The notes on detail 7/A2 do not match notes on detail 2/A3. Please correct this detail. Please call out the connectors for (N) 6X10 cont. ledger to the existing wall. See red marks on detail 2/A3. In detail 2/A3, the connection of 4X6 post to (N) 2X8 joist does not match the sketch on calculation sheet 3. Please correct this detail to show consistency. In detail 1/A3, the (N) 4X10 ledger X24” does not match the sketch on the sheet 2 of calculation. Please modify this detail to show consistency. See other red marks on the drawing sheets: A1, A2, & A3. Please resubmit the marked up set of plans with revised ones.