HomeMy WebLinkAbout197610_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10182358
PROJECT ADDRESS:
2618 S Towner St
PLAN CHECK ENGINEER:
Kwak, JasonTEL:714
647-5866FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/27/2014
INITIAL REVIEW
9/24/2014
EXPIRATION
2/23/2015
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Robert Rios
3.
TEL:
(714)728-1123
FAX:
VALUATION: $11,005.00
EMAIL:
FLOOD ZONE: X-0602320259JAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5866 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2013 California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review.
All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4.1).All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a).
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
-Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
Drawings must be to scale and be on 18" x 24" minimum sheets.
Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper.
Show the North arrow on the plans and centerline of labeled street(s) and alley.
Provide building setbacks to finish of exterior walls to all property lines.
Provide eave / overhang / projection setback to all property lines.Provide wall legend to distinguish between new / existing / demo walls.Provide window and door schedule. Callout sizes and types of openings and if new or existing.Carbon monoxide alarms combined with smoke alarms shall comply with both sections R314 and section R315, all applicable standards, and requirements for listing and approval by the Office of the State Fire Marshal, for smoke alarms.Private garage shall be separated from the residence and its attic by a minimum ½ -in gypsum board applied to the garage side.
Submit engineering calculations for vertical and lateral loads prepared by a registered Civil, Structural Engineer or Architect. Additional Structural Corrections may apply.
Structural framing not using Conventional Light-Frame Construction Provisions of CRC requires the plans and calculations to be signed and sealed by an architect or civil/structural engineer. (CBC 107.3.4)