HomeMy WebLinkAbout190027_4_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10180008
PROJECT ADDRESS:
303 N Spurgeon St
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/31/2013
INITIAL REVIEW
11/2/2013
EXPIRATION
4/29/2014
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Mike Li
3.
TEL:
(917)650-8683
FAX:
VALUATION:$125,000.00
EMAIL:
Yuejunli09@gmail.com
FLOOD ZONE:X-0602320276J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.CBC Sections A106.1 and A106.3.4.1, All drawings and supporting documents shall be prepared, stamped and signed by a California licensed architect or registered civil engineer.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Public Works Agency approval (647-5039)
- County of Orange Health Department approval on the corrected/final set of drawings ((714)433-6000)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceSubmit a signed copy of the contract showing labor and materials for all work to be done under the subject building permit application. The plan check engineer may accept the contract price as the valuation of improvements for unique/unusual projects in lieu of using a cost per square foot basis.Identify existing use.Provide the following:
- Provide a fully dimensioned site plan on each set of plans.
- Disabled access compliance must be shown on the site plan.Show existing entrance door is in compliance with disabled access.CBC Sections 1133B.2.4 and 1133B.2.4.1, Regardless of the occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall be not more than ½” lower than the threshold of the doorway. Change in level between ¼” and ½” shall be beveled with a slope no greater than 1:2. Change in level greater than ½” shall be accomplished by means of a ramp. Provide detailed sections and plan views showing compliance at all doorways requiring accessibility.CBC Section 1133B.2.5, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.CBC Section 1133B.2.6, Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.Provide minimum 60” in length of the bar in compliance with disabled access. CBC 1104.B.5.N/AProvide minimum 60” clear circle at the aisle in the bar.N/AProvide attachment detail for low wall counter at the end.Provide plywood @both sides of the detail 3/A-1 to resists lateral load.N/AProvide minimum 44” clear aisle at the storage area.N/AProvide clear 48” length of landing at door #D.Provide minimum 60” landing at the bathroom door, (door # C)N/AChange the clearance from the toilet to the bathroom tissue dispenser is 7”- 9”.Show urinal is in compliance with disabled access.Show hand sink is in compliance with disabled access.Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC Section 1134B/Chapter 11B:
- An accessible entrance
- An accessible route to the altered areaCBC Sections 1102B, 1124B.1 and 1127B.1. Provide a continuous walking surface from each exit door to public way.Each lot or parking structure where parking is provided for the public as clients, guest or employees, shall provide accessible parking as required by CBC Section 1129B.CBC Section 1115B.4.3 Item 4. Note on the drawings hot water and drain pipes under lavatory shall be insulated.Complete the attached Disabled Accessibility Documentation Form.Note ICC Research Report Number on the drawings for Walk-in cooler and or freezer.Show walk in cooler is in compliance with disabled access.What is the size of the water heater? N/AProvide water heater anchor straps.N/AIdentify if it is type I or type II hood.Is there any type I hood? If there is provide weight, calculation and attachment detail, also I hr shaft.Provide span table for steel studs.Provide spacing for shot pins on detail 5/A1. N/AIs there any alteration to the ceiling? If there is please provide ceiling plan with construction detail.Show height of the storage rack.5/4/2014These Corrections are in addition to the old corrections based on new design.Provide wall legend indicating whether the wall is new , low wall, existing, or being removedProvide complete elevation with dimensions for the bathrooms to show compliance with disabled access.Provide minimum 24” clearance to the strike edge of entry door.\Provide minimum 48” landing at the door at the server station.Sheet 1/A2.1 is not included.Show location of columns from section 1/A2.1 on the floor plan.Show height of the partition wall.Provide complete framing detail for the bathroom ceiling.Provide complete detail for all the soffits , to show how is supported vertically and laterally.Please clarify on the floor plan, if the sink is at the bar counter?CBC Sections 1115B and 1210. Sanitation facility toilet room floors shall have a smooth, hard, non-absorbent surface such as Portland cement, concrete, ceramic tile or other approved material which extends upward onto the walls at least 6”. Walls within 2’ of the front and sides of urinals and water closets shall be similarly finished to a height of 4’.CBC Section 1607.7. Provide complete grab bar details on the drawings showing compliance with CBC Section 1115B.8 including structural strength to support a 250 pound point load.CBC Section 1115B.4.3 Item 4. Note on the drawings hot water and drain pipes under lavatory shall be insulated.CBC Section 1025.9.1. Every occupied portion of any occupancy in Group A that contains seats, tables, displays, and similar fixtures or equipment shall be provided with aisles leading to exits or exit access doorways in accordance with CBC Section 1025.9.1. Aisle access ways for tables and seating shall comply with CBC Section 1014.4.3.CBC Section 1133B.6. Every portion of every building in which are installed seats, tables, merchandise, equipment, or similar materials shall be provided with aisles leading to an exit. Every aisle shall not be less than 36” wide if serving only one side, and not less than 44” wide if serving both sides.All dining, banquet, and bar facilities shall be made accessible to persons with disabilities as provided in CBC Section 1104B.5. At least 5%, but not less than one of the seating spaces in each functional area is accessible as follows:
- Provide a minimum 30” x 48” wheelchair clear floor space.
- Provide knee space at tables at least 27” high, 30” wide and 19” deep.
- Provide height of tables between 28” – 34” from the floor ground.
- Provide access to accessible seating space(s) by aisles with a minimum of 36” in width.Clearly show height and width of the bar accessible to person with disability on the floor plan.Provide minimum 36” clearance at all the walkway, please see red mark.Show how the low walls are being supported laterally.Complete the attached Disabled Accessibility Documentation Form.