Loading...
HomeMy WebLinkAbout198922_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10182795 PROJECT ADDRESS: 1554 Brookhollow Dr Unit# B PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): B, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 10/7/2014 INITIAL REVIEW 11/13/2014 EXPIRATION 4/5/2015 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Darrin Mohacsi 3. TEL: (909)519-1977 FAX: VALUATION:$10,000.00 EMAIL: darrin@ammobros.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.The drawings (the floor plan) submitted for Building Safety Division review is incomplete.The floor plan shall clearly show what is existing, and what is proposed. Clearly show location of all exit doors on the floor plan and locate the new rack systems in a way that they will not block any of the EXIT doors for this building. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2013 California Building Standards Code with local amendments.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceNote on the floor plan the use and occupancy for this building and/or area. Relate each use to a CBC Table item. The recheck of this plan check can be done over the counter. Please call (714)647-5862 and set up an appointment