HomeMy WebLinkAbout195856_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10181817
PROJECT ADDRESS:
2247 S Cedar St
PLAN CHECK ENGINEER:
Heidari, FredTEL:714
647-5862FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
7/17/2014
INITIAL REVIEW
10/15/2014
EXPIRATION
1/13/2015
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Richard Bui
3.
TEL:
(626)548-9719
FAX:
VALUATION:$84,539.00
EMAIL:
nambui1201@gmail.com
FLOOD ZONE:X-0602320278J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2013 California Building Code (CBC); MC = 2013 California Mechanical Code; PC = 2013 California Plumbing Code; EC = 2013 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.
All drawings and supporting documents shall be stamped, and signed by a California licensed architect or registered engineer. All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a).
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.]
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Public Works Agency approval (647-5039).
-Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper.
Show how dwelling is provided with comfort heating facilities capable of maintaining a room temperature of 68oF at a point of 3 feet above the floor in all habitable rooms. (1204)
The residence shall conform to the State Energy Conservation Standards. Submit forms and calculations for review and blueprint the final forms on the plans.
-Signed Energy Efficiency Documents must be printed on the plans.
-Also, submit 2 copies of signed Energy Efficiency calculations.
-The permit applicant shall be responsible for obtaining an energy plan check from a consultant
who is qualified to perform an energy efficiency analysis in accordance with the California Code
of Regulations (CCR), Title 24, Part 1 (Administration) and Part 6 (2013 California Energy Code).
The plan check consultant must sign documentation certifying that a thorough, competent review
has been performed on behalf of the Enforcement Agency.
-Refer to the attached public handouts titled “Energy Efficiency Compliance” and “Energy
Efficiency Compliance Documentation”.
Show Radiant Barrier, Cool Roofing, Duct Ceiling as required by the 2013California Energy Residential Manual.
The following are required for attached garage:
- Specify one-hour fire-resistive construction (example is 5/8 “Type-X” drywall on 2x4 framing) on
the garage side for walls, ceilings, posts, and beam of garage adjacent to or supporting the dwelling.
-Door may swing into the garage if floor or landing in the garage is not more than 0.50 inch lower than the door threshold. Changes in elevation between 0.25 and 0.50 shall have a 2:1 bevel.