Loading...
HomeMy WebLinkAbout200689_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10183444 PROJECT ADDRESS: 101 S Harbor Blvd PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/15/2014 Existing Restaurant INITIAL REVIEW 12/18/2014 EXPIRATION 6/13/2015 RECHECKS: 1.1-21-15 PROJECT APPLICANT CONTACT PERSON: 2. Steve Shaw 3. TEL: (310)773-7772 FAX: VALUATION:$47,300.00 EMAIL: Steve@adnarch.com FLOOD ZONE:X-0602320256J Re-check: 1-21-15 Called architect to provide signed contact for correct valuation and to resolve accessibility issues with existing toilet rooms. APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3 corrected sets of plans.(When meeting is needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information. Please remove electrical, mechanical and plumbing sheets.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - County of Orange Health Department approval on the corrected/final set of drawings (667- 3600) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceComplete all soffit and furred out wall details. Provide complete positive connection detailing, including number, type, location of fasteners and how attachment is made to the building structure. Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use. Note on drawings: - Provide mechanical ventilation for each area/room in accordance with the 2013California Mechanical Code. Note on drawings: Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use.Exit illumination and exit sign requirements in accordance with CBC Section 1011 shall be shown on the drawings. Be specific as to the type of exit signs to be installed.Tactile exit signs shall be required at the following locations:- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3.Note type of safety glazing complying with CBC Section 2406 for glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24” arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60” above the walking surface.Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636. In lieu of providing structural calculations, note ICC Research Report Number on the drawings for the suspended ceiling system. (ICC Report Number 1308 or other approved products)Drawings submitted to the Building Division for review shall provide the following information/drawings to insure compliance with CBC Division 2; - An accessible entrance - An accessible route to the altered area - Accessible restrooms - Accessible telephone (if any) - Accessible drinking fountains, and - Parking, signage and alarmsIt is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. If applicable please remove notes referring to ADA compliance from drawings. This project is reviewed for compliance with State Accessibility StandardsComplete the attached Disabled Accessibility Documentation FormRevise existing floor plan of toilet rooms to show compliance with Section 11B-603.Provide completely dimensioned floor plans, elevations and sections of sanitary facility insuring wheelchair clearances. Separate, disabled accessible, sanitary facilities shall be provided for each gender when required by Table 4-1 for each occupancy type. Minimum of two toilet rooms are required.For revised toilet room, Provide complete grab bar details on the drawings showing compliance with CBC Section 1115B.8 including structural strength to support a 250 pound point load.Note on the drawings hot water and drain pipes under lavatory shall be insulated.For revised Sanitation facility toilet room floors shall have a smooth, hard, non-absorbent surface such as Portland cement, concrete, ceramic tile or other approved material which extends upward onto the walls at least 6”. Walls within 2’ of the front and sides of urinals and water closets shall be similarly finished to a height of 4’.Check Stands CBC Table 11B-2. Check stands must be accessible to both employees and customers. Please refer to plan check comment below: NUMBER OF REGULAR NUMBER TO BE CHECKSTANDS ACCESSIBLE 1 to 4 1Provide accessible bar seating for wheel chair accessibility at 34” (max.) height.Indicate the top of fixed or built-in counter, tables is between height of to be at 28” to 34” above the finish floor and knee clearance to be a minimum of 27” high, 30” wide, and 19” deep. One of each type of station shall be located at a section of counter that is at least 60” long and no more than 28 to 34” high. Counter area to be accessible for both employee and customers including cash register counter. All dining, banquet, and bar facilities shall be made accessible to persons with disabilities. At least 5%, but not less than one of the seating spaces in each functional area to be accessible as follows: - Provide 60” length counter for A2 occupancy. -Provide a minimum 30” x 48” wheelchair clear floor space. - Provide knee space at tables at least 27” high, 30” wide and 19” deep. - Provide height of tables between 28” – 34” from the floor ground. - Provide access to accessible seating space(s) by aisles with a minimum of 36” in width.Every portion of every building in which are installed seats, tables, merchandise, equipment, or similar materials shall be provided with aisles leading to an exit. Every aisle shall not be less than 36” wide if serving only one side, and not less than 44” wide if serving both sides. Provide dimensions to insure compliance on the drawingsProvide enlarged plan of accessible parking and ramp including truncated dome to insure accessibility compliance.Provide parking data on the site plan showing the total number of parking spaces provided the number of disabled accessible spaces and the number of van accessible spaces, showing compliance with CBC Table 11B-6208.2 of CBC. Please refer to red marks on the drawings for additional plan check comments. Indicate 2% slope max for accessible parking and path of travel on the drawings.One in every eight accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible. The words NO PARKING shall be painted on the ground within each eight’ loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide.Provide site plan showing location of 6” curb (Double line) landscape area and zero curb area to clarify locations where truncated dome is required. Detectable Warning Product Approval. Only approved Division of the State Architect, Access Compliance (DSA/AC) approved detectable warning products.Provide on the drawings a complete door schedule, showing: - Hardware complying with exiting and disabled accessibility requirements (CBC Sections 1008.1.8 andProvide legible door schedule on sheet A11.The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. Show 18” clearance for door number to new toilet room.The floor or landing at each side of an exit door shall be level and having a length in the direction of the door swing of at least 60” and the length opposite the direction of door swing of 48” as measured at right angles to the plane of the door in the closed position. Provide door clearance for new toilet room.Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.Incorporate results of structural calculation (HTK, structural engineers) for new awning and signage into drawings. Revise detail 1 on sheet 5 to match calculations. Revised structural detail/s to be signed and stamped by engineer of records, HTK.Please refer to red marks on the drawings for additional plan check comments.