HomeMy WebLinkAbout198863_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10582774
PROJECT ADDRESS:
701 E Fifth St
PLAN CHECK ENGINEER:
Heidari, FredTEL:714
647-5862FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/9/2014
INITIAL REVIEW
2/3/2015
EXPIRATION
6/7/2015
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Anthony Sagginario
3.
TEL:
(626)905-3049
FAX:
VALUATION:$20,000.00
EMAIL:
tony@niceremodel.com
FLOOD ZONE:X-0602320276J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2013 California Building Code (CBC); MC = 2013 California Mechanical Code; PC = 2013 California Plumbing Code; EC = 2013 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.
All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered engineer. All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a).
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.]
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
-Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
No water closet shall be set closer than 15 inches from its center to any side wall or obstruction, nor closer than 30 inches center to center to any similar fixture. The clear space in front of any water closet shall not be less than 24 inches. Show compliance for new water closets in unit 13.
Wall covering shall be cement plaster, tile or approved equal to 72 inches above drain at showers or tub with showers. Materials other than structural elements shall be moisture resistant. Net area of shower receptor shall be not less than 1,024 sq. in. of floor area, and encompass 30-inch diameter circle. Show compliance for the new showers.
In every sleeping room of dwelling units, at least one openable emergency escape and rescue window or door shall open directly into a public street, pubic alley, yard or exit court, meeting all of the following:
- An openable area of not less than 5.7 square feet (5.0 square feet for ground-floor openings);
-A minimum 24 inch clear openable height;
-A minimum clear openable width of 20 inches;
-A sill height not over 44 inches above the floor.
-show compliance for the new bedrooms.Provide and show the location of smoke alarmin each sleeping room.Provide and show the location(s) of Carbon monoxide alarmin each unit.
Show how dwelling is provided with comfort heating facilities capable of maintaining a room temperature of 68oF at a point of 3 feet above the floor in all habitable rooms.
Show compliance with the California Green Building Standards Code Section 301.1.1 for replacement of noncomplianceplumbing fixtures.