HomeMy WebLinkAbout205745_3_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10185104
PROJECT ADDRESS:
2610 S Birch St
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
III B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/18/2015
Loading Dock only, outdoor
INITIAL REVIEW
5/20/2015
EXPIRATION
11/14/2015
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Ronald McCurry
3.
TEL:
(909)268-8143
FAX:
VALUATION:$35,000.00
EMAIL:
rmccurry@rexfordindustrial.com
FLOOD ZONE:X-0602320278J
APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Resubmit 3 corrected sets of plans.(When needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceReference Sheet 1; clarify if two ramps located on the West of building is part of this permit, newor existing. Additional plan check comments may apply.Reference sheet S-2, Provide a ramp legend to clarify ramp as shown at bottom of page is new or existing. Is this ramp to be demoed? Is this ramp part of accessible exiting system of building?Provide dimensions for detail 3 of Sheet S-1 and provide legible “Project Statistic” detail A.
Reference Sheet 16 of structural calculations, In lieu of soils investigation report per Sections 1803.6 of the 2013 California Building Code, revise structural calculations for minimum foundation/footing design requirements for small projects as follows:
- Allowable foundation pressure not to exceed 1000 PSF.
- Footing to have minimum reinforcement of: 2 #4 at top and 2 #4 at bottom.Valuation of proposed project is calculated as $35,000.00. A minimum of 20% of valuation of construction is required to be spent towards providing disabled access in the priority order noted below. Revise the drawings to show compliance. Drawings submitted to the Building Division for review shall provide complete drawings to provide the following information to insure compliance with CBC Division 2, Chapter 11B:
- An accessible entrance
- An accessible route to the altered area
- Accessible restrooms
- Accessible telephone (if any)
- Accessible drinking fountains, and
- Parking, signage and alarms