Loading...
HomeMy WebLinkAbout207660_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10485764&10485765 PROJECT ADDRESS: 611 W Civic Center Dr PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 8/21/2015 INITIAL REVIEW 9/16/2015 EXPIRATION 2/17/2016 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Jimmy Chen 3. TEL: (951)454-6206 FAX: VALUATION:$14,360.00 EMAIL: jcc3361@hotmail.com FLOOD ZONE:X-0602320163J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Please return marked up set of drawings with corrections.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2013 California Building Standards Code with local amendments. Provide Energy documentation.Additions, alterations or repairs made to any building constructed prior to January 1, 1946, other than an R-Occupancy building, exceeds $50,000 in cost in any one-year period, then either (A) the entire building must be completely sprinklered in accordance with fire department standards, or (B) the building must comply with requirements as outlined under Santa Ana Municipal Code (SAMC) Section 8-150. A copy of SAMC Section 8-150 may be obtained by visiting the City of Santa Ana’s website at www.santa-ana.org.Clearly indicate the scope of work under this building permit application: - Revise project job description on the building permit application worksheet to reflect the work to be done under the subject building permit application. - Construction drawings must clearly show all work to be done under the subject building permit application. - Delete all notes and details from drawings that are not a part of the work to be done under the subject building permit application. This includes mechanical, plumbing and electrical work that is not specifically required by the Building Code.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - County of Orange Health Department approval on the corrected/final set of drawings (667- 3600) - School District Compliance Certificate; a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of work. Refer to the attached handout. - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide the following: - Provide a fully dimensioned site plan on each set of plans. - Disabled access compliance must be shown on the site plan. - Show all property lines of record on the site plan. Show compliance with CBC Section 704 and CBC Tables 601, 602, and 704.8.Show on the plans: - Complete legal description - Assessor’s Parcel Number - Project Address/Suite/Room Numbers; Building Numbers - Occupancy Classification(s) - Type of Construction - Area tabulation justifying floor area(s) of building(s) (CBC Sections 503, 505, 506, 507, and 508 and CBC Table 503) - Fire Sprinkler System (State purpose of sprinkler system, for example, area increase under CBC Section 506.3, required by CBC Section 903 for type of occupancy, etc.) - Number, width, and purpose (cite code section) of yards required - Number and fire-resistive rating of all area separation walls - Number of stories/mezzanines and building height in feetProvide a wall legend indicating whether the wall is: - Existing, new, or to be removed - A fire-resistive assembly - Bearing walls versus non-bearing partitionsWhen there has been a change in use or occupancy classifications, drawings shall show compliance with the CBC requirements for the new classifications. Reference CBC Section 3406.Provide on the drawings a complete “fire resistance design schedule” which shall include the following: - The building elements which require fire-resistive construction. - The hourly rating of the building element as required by the Code. - Evidence of appropriate fire resistance for each building element in accordance with specific UL listing or ICC Evaluation Report for each material selected. Evidence shall include appropriate material thickness for each building element. - Non-standard fire-resistive designs requiring adhesives, overcoats, metal lath-netting, or special thicknesses shall be detailed.On sheet A-0, provide a complete site plan. Total of 46 parking stalls are provided on site, minimum two parking stalls shall be accessible. At least one accessible parking stall shall be a “Van” space. Provide accessible parking details and dimensions on plan.Site plan show a “Storage” area adjacent to parking space. However, floor plan on sheet A-1 shows “Food Retail”. Verify discrepancy and provide cross references on the plan.Sheet A-0 indicates retaining wall and free-standing wall detail. Provide the following information:Specify lap-splice length or minimum embedment into existing CMU.Specify horizontal rebar spacing.Provide structural design calculations if the total height is greater than 7 feet or the retained height are greater than 3 feet.Specify the maximum height of wall.Site plan indicates accessible parking spaces and access ramp, Provide details.On sheet A1, Provide shear-transfer connection on all details.On sheet A1, provide footing on all detail.On sheet A1, cross reference proposed building location from the site plan. Show Fire-Separation Distance from the building to the property line.The retail space is being converted from an open space to a habitable space. Provide Energy documentation for plan check.On sheet A1, It is unclear the type of work being proposed in the lobby area. Provide notes or details to clarify design.On sheet A3, provide structural details for new partition wall.On sheet A3, clarify the scope of work in bathrooms.On sheet A4, make cross reference from the site plan.