Loading...
HomeMy WebLinkAbout210330_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10186659 PROJECT ADDRESS: 4717 W First St PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: N/A OCCUPANCY CLASSIFICATION(S): N/A PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 9/28/2015 INITIAL REVIEW 10/6/2015 EXPIRATION 3/26/2016 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Tran Dien 3. TEL: (714)262-0933 FAX: VALUATION:$10,000.00 EMAIL: trandien@yahoo.com FLOOD ZONE:A-0602320256J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceIt is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. Accessible parking spaces serving a particular building shall be located on the shortest accessible route of travel from adjacent parking to an accessible entrance. Please make a note on the plan for location of entrances to this existing building with respect to accessible parking stalls.Provide parking data on the site plan showing the total number of parking spaces provided, the number of disabled accessible spaces and the number of van accessible spaces, showing compliance with CBC Section 11B-208.2.and CBC Table 11B-802.2.(Seems to be 134 parking spaces are provided and only 4 accessible spaces are shown). CBC Table 11B-208.2 establishes the number of accessible parking spaces required. Revise the drawings to show at least5disabled accessible parking spaces including1van accessible spaces.CBC Section 11B-208.4. One in every six accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible.Any truncated domes for the “ADA LOADING RAMP” As shown on the sheet SP?Please make sure that the referenced code sections are update on the plan. See red on the plan.The building data on sheet T shall be updated as marked on the plan.The recheck can be done over the counter. Please call 714-647-5862 to schedule an appointment for over the counter recheck.