HomeMy WebLinkAbout212387_1_Corrections.docx PLAN CHECK NO: 10187445 PROJECT ADDRESS: 318 W Fifth St PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/7/2015 INITIAL REVIEW 1/26/2016 EXPIRATION 6/4/2016 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Jeff Beddow 3. TEL: (949)722-7400 FAX: (949)722-8855 VALUATION:$133,548.00 EMAIL: jeff.saproperties@gmail.com FLOOD ZONE:X-0602320276J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Sheet A-0Please revise the type of construction to “V-B”. See attached record for reference.Please provide note or detail to show one-hour separation between proposed Business occupancy in the basement and existing Assembly occupancy on the first floor. Per 2013 CBC Table 508.4, one hour separation construction is required between Assembly occupancy and Business occupancy with fire sprinkler.Please erase “2001 UMC” code reference under Project Summary – Applicable Code.Sheet A-2Specify 18 inches strike-edge dimension at the pull-side of the door in Room “119”. 11B-404.2.4.1 Swinging doors and gates.Swinging doors and gates shall have maneuvering clearances complying with Table 11B-404-2.4.1.Provide an Exit analysis plan. Show number of occupants at occupied spaces. Show travel distance to exits.Show overall-diagonal distance.Use dotted line or dashed line to indicate egress path of travel and number of occupants along the egress path.Show egress width capacity exceeds the calculated egress width.Sheet A-9 – Detail 3Specify tactile character height position as follow:11B-703.4.1 Height above finish floor or ground. Tactile characters on signs shall be located 48 inches minimum above the finish floor or ground surface measured from the baseline of the lowest Braille cells and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest line of raised characters.