PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10187682
PROJECT ADDRESS:
3370 S Bristol St
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
667-2743FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
M
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/17/2015
INITIAL REVIEW
2/5/2016
EXPIRATION
6/14/2016
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Stefan Colvey
3.
TEL:
(909)910-5022
FAX:
VALUATION:$10,000.00
EMAIL:
Scolvey@accoes.com
FLOOD ZONE:X-0602320259J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 667-2743 for an appointment.All drawings shall be signed by the person who prepared these plans and specifications.Include address and telephone number of the responsible designer, and date of signing of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans
should be submitted to expedite the process.
The valuation of improvements for the subject building permit application has been calculated to be $10,000.Dimension the maximum height of the angle located at the end of the brace.Engineer of record should sign and stamp the plan.Call out the welding of the angle to the base plate.Provide a detail of the connection of the proposed 2X to the existing beams.Add a note to the plans indicating that all welding to be done in an approved shop and that a copy of the certificate should be submitted to the inspector or plan check engineer.Please clarify why the allowable value of the lag bolt is being multiplied by 2 twice; the member is not in double shear and the Load duration factor is 1.6.