PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10187714
PROJECT ADDRESS:
3400 W Warner Ave Unit# F1
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
647-5848FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
M
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/23/2015
INITIAL REVIEW
2/11/2016
EXPIRATION
6/20/2016
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Sean Fotheringham
3.
TEL:
(714)496-3199
FAX:
VALUATION:$15,000.00
EMAIL:
Sean@spectrumspacedesign.net
FLOOD ZONE:X-0602320258J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.All drawings shall be signed by the person who prepared these plans and specifications.Include address and telephone number of the responsible designer, and date of signing of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840).
- Public Works Agency approval (647-5039).
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance.The valuation of improvements for the subject building permit application has been calculated to be $15,000.00.Provide a wall legend indicating whether the wall is:
- Existing, new, or to be removed
- A fire-resistive assembly
- Bearing walls versus non-bearing partitionsNote on the floor plan the use and occupant load of each room and/or area based on CBC Section 1004 and Table 1004.1.1. Refer to Table 1015.1 for spaces with one means of egress based on maximum occupant load.Provide typical full height cross sections through new partitions showing:
- Size, spacing, and material of framing members.
- Note gauge and ICC Research Report number and installation/construction requirements for metal framing
members.
- Provide on the drawings details for the lateral support of partitions, rails and similar space dividers.
- Fire-blocks in combustible construction in accordance with CBC Section 717. Show location(s) and provide
typical construction details.According to the code enforcement notes, suite F1 was never permitted. The Tenant improvement plans is to create suit F1, hence all the walls between F and F1 are new. In addition the tenant improvement includes suit F. Provide a floor plan of suit F to show compliance with exiting, and accessible means of egress.