HomeMy WebLinkAbout213266_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10187691
PROJECT ADDRESS:
2155 S Hathaway St
PLAN CHECK ENGINEER:
So, AnsonTEL:714
647-5830FAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
F-1, H-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/21/2015
INITIAL REVIEW
1/4/2016
EXPIRATION
6/18/2016
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Sean Fotheringham
3.
TEL:
(714)496-3199
FAX:
VALUATION:$150,000.00
EMAIL:
Sean@spectrumspacedesign.net
FLOOD ZONE:X-0602320276J
APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Please return marked up set of drawings with corrections.Sheet A-1Scope of Work indicates a proposed new collector at the back of the building. Show the proposed new collector location on the site plan.Please include the new chain-linked fence under Scope of Work.Provide note on the title sheet: “ Spray Booth design per separate permit”.Sheet A2.1Please delete the following note on plan:” 25’-0” PER CBC TABLE 1021.2”. Two exits are required at the Hazardous Occupancy area. Therefore, the one exit requirement is not applicable at the Exit Access door to the door of Exit.Identify the usage of room number “104”.Please cross-reference detail number “A/A2.1” at proposed wall between room “104” and room “108”.The proposed wall layout does not match the wall layout on the equipment plan on sheet S-1. Verify discrepancy.Plan shows the proposed room “108” as “F-1 occupancy”. However, Equipment plan shows a hazardous occupancy.Show occupant load number in room “108”. Room with equipment usage shall have occupant load factor of 300 per 2013 CBC Table 1004.1.2. Provide note to verify existing side-lights near door number 9 has tempered glazing.Structural CalculationsStructural calculations page 2 shows 3’-0”x 3’-0”x 15” inch deep footing is required to support the new equipment. However, the footing is not shown on plan.