HomeMy WebLinkAbout220203_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10189893 PROJECT ADDRESS: 2205 N Westwood Ave PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 7/7/2016 INITIAL REVIEW 7/13/2016 EXPIRATION 1/3/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Andre Tardif 3. TEL: (714)412-0371 FAX: VALUATION:$20,000.00 EMAIL: andytardif@gmail.com FLOOD ZONE:X-0602320144JPlease indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Public Works Agency approval (647-5039). -Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. Wall covering shall be cement plaster, tile or approved equal to 72 inches above drain at showers or tub with showers. Materials other than structural elements shall be moisture resistant. Note ā€œNā€ on sheet A-2 shall be updated. Show the location(s) of smoke alarm(s) with a battery back up in each sleeping room and at a point centrally located in the corridor or area giving access to each sleeping area. Show location(s) of carbon monoxide alarm on the floor plan. The City has encountered a large number of inspection problems arising from a lack of specific framing details. The following listed items are required to be shown on the plans: -All plumbing walls are to be framed with a minimum of 6" studs. -Permissible notching and boring of joists are to be shown on the plans and shall not exceed CRC Bath room exhaust fan to be equipped with humidity control per CRC Section 303.3.1. See red marks on sheet A-8. The occupancy group for this project is R-3. Please update the note on sheet A-1. Recheck could be done over the counter. Please set up an appointment for over the counter recheck.