PLAN CHECK NO:
10189401
PROJECT ADDRESS:
610 N Patricia Ln
PLAN CHECK ENGINEER:
So, AnsonTEL:714
647-5830FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
6/2/2016
INITIAL REVIEW
7/20/2016
EXPIRATION
11/29/2016
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Araceili Maciel
3.
TEL:
(714)285-1121
FAX:
VALUATION: $44,363.00
EMAIL:
aadrafting@msn.com
FLOOD ZONE: X-0602320163J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2013 California Residential Code (CRC); 2013 California Building Code (CBC); CMC = 2013 California Mechanical Code; CPC = 2013 California Plumbing Code; CEC = 2013 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2013 California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review.
Sheet A-1
Show drainage and slope away from the new addition on the site plan.
Sheet S-1 Show header size at bedroom #4 window.Specify eave over-hang dimension facing property line. In addition, one-hour fire protection detail is required where the over-hang eave is located between 2 foot to 5 foot from property line. Specify detail “16/SD1” along bedroom #5 exterior wall.