HomeMy WebLinkAbout218704_3_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10189442
PROJECT ADDRESS:
3232 S Fairview St
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
6/7/2016
DHL TI and full accessibility compliance
INITIAL REVIEW
6/21/2016
EXPIRATION
12/4/2016
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Mickey Tedder
3.
TEL:
(951)870-0304
FAX:
VALUATION:$150,000.00
EMAIL:
Mickey@bcccontracting.com
FLOOD ZONE:X-0602320258J
APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Please refer to red marks on both architectural and structural drawings for additional plan check comments. Return marked up set of drawings with corrections.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance of Worker’s Compensation Insurance.Please note all accessibility comments are based on July 1st 2015 Supplements of 2013 CBC. Drawings are required to show compliance.Please note that full building and site accessibility compliance is required for this permit based on DHL agreement letter dated May 19, 2016. Drawings are incomplete and do not show compliance.For B occupancy show compliant path of travel compliance with followings: Exits shall be so located on each story such that the maximum length of exit access travel, measured from the most remote point within a story to the entrance to an exit along the natural and unobstructed path of egress travel, shall not exceed the distances given in Table 1019.2 and Table 1016.1. Table 1016.1 Exit Access Travel Distance:
OCCUPANCY WITHOUT SPRINKLER WITH SPRINKLER SYSTEM (feet) SYSTEM (feet)
B200300cTable 1019.2 For Buildings With One Exit: (Show compliance with office area with one exit)Maximum Height Maximum OccupantsOf Building
Occupancy Above Grade PlanePer Floor And Travel Distance
B, 1 Story49 occupants and 75’ travel distanceExiting through storage, warehouse, manufacturing and similar uses is not permitted from office areas.Clarify on the drawings that the rated wall and all opening including windows and doors are 1 hour fire rated. Identify location of full height wall on the drawings and provide door and window schedule to show 60 minute fire rating for openings. Table 508.4 of CBC. Please refer each fire rated assembly to Table 7 of 2013 CBC and provide a copy of description of rated assembly on the drawings. Plans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Section 106.1.1 and CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana.Note on the drawings for compliance with light and ventilation per Section 1201 of 2013 CBC.Drawings are missing information to review accessibility compliance with Division 2, Chapter 11B of 2013 CBC. Provide drawings to show compliance with followings: - An accessible entrance
- An accessible route to the altered area
- Accessible restrooms
- Accessible telephone
- Accessible drinking fountains, and
- Parking, signage and alarms It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA Standards and it is the responsibility of designer. If applicable please remove notes referring to ADA compliance from drawings. This project is reviewed for compliance with CBC, California Building Code. Sanitary facilities serving the area of new work shall be disabled accessible. Provide fully dimensioned floor plan including elevations to show compliance with CBC Section11B, Division 6. Tactile exit signs shall be required at the following locations: (identify location of each applicable signage on the floor plan or reflected ceiling plan.
- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”
- Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be
identified by a tactile exit sign with the following words as appropriate:“EXIT STAIR DOWN”“EXIT RAMP DOWN”“EXIT STAIR UP”“EXIT RAMP UP”
- Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual
exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”
- Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.”At every entrance and at every major junction along or leading to an accessible route of travel, there shall be a sign displaying the international symbol of accessibility. Signs shall indicate the direction to accessible building entrances and facilities. Show location of path of travel including slope and cross slop on the drawings. . If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide. Provide enlarge plan of parking and entrance to building to show accessibility compliance including Entrance door, Path of travel and parking spaces and signage. Show compliance with CBC Table 11B-208.2, for number of accessible parking spaces required for existing building. Provide parking data on the site plan showing the total number of parking spaces provided the number of disabled accessible spaces and the number of van accessible spaces. Surface slopes of accessible parking spaces shall be the minimum possible and shall not exceed 1 unit vertical to 48 units horizontal (2% slope) in any direction.Disabled accessible parking spaces should be sized as follows and in compliance with Division 5 of Chapter 11-B.:
- CBC Section 1129B.3, Item 1. Where single spaces are provided, they shall be a 9’ wide parking area with
an outlined 5’ wide (8’ wide for van accessible space) loading and unloading aisle ON THE PASSENGER SIDE
OF THE VEHICLE. The minimum length of each parking space shall be 18’. The loading and unloading access
aisles shall be marked by a border painted blue. Within the blue border, hatched lines a maximum of 36” on
center, shall be painted a color contrasted with the parking surface, preferably blue or white. Parking access
aisles shall be part of an accessible route of travel) to the building or facility
entrance. Parked vehicle overhangs shall not reduce the clear width of an accessible route. The words NO
PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be
painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials.
When more than one space is provided, two 9’ wide parking areas may be
outlined on each side of a 5’ wide (8’ wide for van accessible space(s)) loading and unloading aisle. The
minimum length of each parking space shall be 18’. The loading and unloading access aisles shall be marked
by a border painted blue. Within the blue border, hatched lines a maximum of 36” on center, shall be painted
a color contrasted with the parking surface, preferably blue or white. Parking access aisles shall be part of an accessible route of travel to the building or facility entrance. Parked vehicle overhangs shall not reduce the clear width of an accessible route. The words NO PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. Revise the drawings to show the words NO PARKING shall be painted on the ground within each loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officials. Provide parking space identification in accordance with CBC Division 5 including:
- Each parking space reserved for persons with physical disabilities shall be identified by a reflecting sign
permanently posted immediately adjacent to and visible from each stall or space, consisting of a profile view of
a wheelchair with occupant in white on dark blue background. The sign shall not be smaller than 70 square
inches in area and, when in path of travel, shall be posted at a minimum height of 80” from the bottom of the
sign to the parking space finished grade and shall be un-obscured by a parked vehicle. Signs may also be
centered on the wall at the interior end of the parking space. An additional sign or additional language below
the symbol of accessibility shall state “Minimum Fine $250.”
- An additional sign shall also be posted in a conspicuous place at each entrance to off-street parking facilities,
or immediately adjacent to and visible from each stall or space. The sign shall not be less than 17” by 22” in
size with lettering not less than 1” in height, with clearly and conspicuously states the following:Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards or license plates issued for persons with disabilities may be towed away at owner’s expense. Towed vehicles may be reclaimed by telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a.
- Provide assurance on the drawings that existing signage language reflects the paragraph above.Show compliance with CalGreen and SB 407 and provide completed Forms on the drawings to insure compliance. Please note that additional plan check comments may apply to this project.Provide separate architectural and structural drawings. Incorporate results of structural calculations into drawings prior to re-submittal. Show location and weight of new and existing equipment/s on the roof framing plan. Indicate the height of retaining wall for new truck well. Calculation for design and justification may be required.Additional plan check comments may apply to this project.