HomeMy WebLinkAbout221430_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10190299 PROJECT ADDRESS: 1020 N Towner St PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 8/8/2016 INITIAL REVIEW 8/20/2016 EXPIRATION 2/4/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Araceli Maciel 3. TEL: (714)285-1121 FAX: VALUATION: $48,555.00 EMAIL: aadrafting@msn.com FLOOD ZONE: X-0602320144J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2013 California Residential Code (CRC); 2013 California Building Code (CBC); CMC = 2013 California Mechanical Code; CPC = 2013 California Plumbing Code; CEC = 2013 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2010 California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review. Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a). This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). - Public Works Agency approval (647-5039). - Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. - In addition to other fees, a "Park Acquisition and Development Fee" in the amount shown below shall be required pursuant to a resolution of the City Council for the Recreation and Community Services Agency; net addition of ________ bedroom(s).Amount of $5,998.43; net addition of 5 bedroomsAmount of $5,391.50; net addition of 4 bedroomsAmount of $4,869.15; net addition of 3 bedroomsAmount of $3,629.16; net addition of 2 bedroomsAmount of $2,723.74; net addition of 1 bedroom Drawings must be to scale and be on 18" x 24" minimum sheets. Scale of Drawings must be large enough to insure legibility. Delete notes and details that do not apply to this project. Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper. Delete notes and details that do not apply to this project. (CBC 107) Specify finish floor elevation of first floor. (CBC 107.2.5) Prior to the issuance of building permit(s), tract maps, parcel maps, lot line adjustments, public way abandonments, covenant, conditions and restrictions (CC&R's), etc., related to the subject project must be legally recorded with the County of Orange.Sheet A-1 Provide existing and proposed contours/spot elevations to indicate general site slope and drainage pattern. (CBC 107) Lots shall be graded to drain surface water away from foundation walls. The grade shall fall a minimum of 6 inches within the first 10 feet. (CRC R401.3) Enlarge Texts on Energy Forms. Sheet A-2 Show attic access location for the new addition. In addition, specify size with dimensions. Sheet A-3Provide foundation ventilation calculations and ventilations vents provided.Sheet S-1Provide ridge to rafter structural connection detail on framing plan.Provide structural design calculations on the 3.5x9.25 Paralam beam.