Loading...
HomeMy WebLinkAbout220637_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10190037 PROJECT ADDRESS: 1951 E Dyer Rd Bldg# A PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: III A, SPK OCCUPANCY CLASSIFICATION(S): R-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 8/22/2016 INITIAL REVIEW 9/1/2016 EXPIRATION 2/18/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Keith Minnie 3. TEL: (714)221-8334 FAX: VALUATION: $52,800,000.00 EMAIL: keithm@architectsorange.com FLOOD ZONE: X-0602320278J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2013 California Residential Code (CRC); 2013 California Building Code (CBC); CMC = 2013 California Mechanical Code; CPC = 2013 California Plumbing Code; CEC = 2013 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3 corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2013California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review. Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees. All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4.1).All persons preparing plans for others shall sign those plans. Business and Professions Code Chapter 3, Division 3, Section 5536.1 (a). This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). - Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). -Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. -Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039). In addition to other fees, a "Park Acquisition and Development Fee" in the amount shownbelow shall be required pursuant to a resolution of the City Council for the Recreation andCommunity Services Agency; net addition of ________ bedroom(s).Amount of $6,622.22; net addition of 5 bedroomsAmount of $5,952.18; net addition of 4 bedroomsAmount of $5,375.50; net addition of 3 bedroomsAmount of $4,006.57; net addition of 2 bedroomsAmount of $3,006.99; net addition of 1 bedroom Drawings must be to scale and be on 18" x 24" minimum sheets. Scale of Drawings must be large enough to insure legibility. Delete notes and details that do not apply to this project. Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper. Delete notes and details that do not apply to this project. (CBC 107) New one- and two-family dwellings and townhouses shall have an automatic fire sprinkler system installed in accordance with CRC Section R313.3 or NFPA 13D. Contact the Santa Ana Fire Department for fire sprinkler permit requirements (714) 647-5839. (CRC R313) Specify finish floor elevation of first floor. (CBC 107.2.5) State Division of Occupational Safety Permit (Cal/OSHA) (939-0145). -Construction of trenches or excavations, which are five feet or deeper and into which a person is required to descend. -The construction or demolition of any building, structure, false-work, or scaffolding more than three stories high or the equivalent height. Provide pedestrian protection in accordance with CBC Section 3306. Show location and type of protection on plan view. Provide typical construction details, sections, and elevations of pedestrian protection required. Pedestrian protection constructed within a public right of way shall require a building permit issued by the Building Safety Division and a separate approval from the City's Public Works Agency (647-5039). The project owner/developer shall designate a contact person who has the authority to act on behalf of the owner to coordinate and provide consistency for all of the plans required for the project including landscaping, grading, pedestrian protection, architecture, structural, electrical, mechanical and plumbing. On the drawings note the contact person's name, position, address and telephone number. (CBC 107.1 and 107.3.4.1) Prior to the issuance of building permit(s), tract maps, parcel maps, lot line adjustments, public way abandonments, covenant, conditions and restrictions (CC&R's), etc., related to the subject project must be legally recorded with the County of Orange. PLAN CHECK COMMENTS Sheet A3.35 – Specify truncated dorm detail where pedestrian route crosses vehicular traffic ways. Sheet A7.1.2 – Door “212”, Sheet A7.1.3- Door “312”, Sheet A7.1.4- Door “412”, Sheet A7.1.5 – Door “512”: The assumed property line is located along grid-line “R”. The Fire Separation distance is between 0 to less than 3 feet. Per CBC Table 705.8, openings are not permitted. Verify openings on door “212”, “312”, “412”, and “512”. Sheet A1.5 – Floor plan shows garage stairway located near room “449” terminates on the fourth floor. It appears the stairway was designed as a second exit on the 6th floor of the garage due to the number of occupant load increased from the swimming pool area. Once the occupants reached the vertical exit enclosure, the level of fire protection shall maintain throughout until occupants reaches the exit discharge. On the fourth floor, the vertical enclosure terminates at the one-hour corridor of the building. In order to maintain the same level of fire protection as the vertical stairway enclosure, the corridor shall be designed as an exit passageway per CBC Section 1023. The issue with this design is the openings at storage doors at the corridor. Openings at the exit passageways are limited to the exit-access space necessary for exit and exterior exit. Sheet A2.2-Fourth Floor – 10 Fire walls are utilized in this building in order to lower the Type of Constructions required for the entire building. The fire areas were reduced to the maximum allowable area per story and per building on a Type III-A construction. Per CBC Section 706.1, each portion of a building separated by one or more fire walls that comply with the provisions of this section shall be considered a separate building. When fire walls are considered as separate buildings, other Code provisions shall follow these criteria such as allowable area design in chapter 5 and Type of construction design in chapter 6. On egress system design, each building shall have its own egress system consist of exit access portion, exit portion, and exit discharge portion in accordance with CBC chapter 10. There are “buildings” on this structure do not have its own vertical exit enclosure. Exit system is designed using travel distance to another “building”. For example, the “building” on the East side of the garage require occupants on the fourth floor travel pass through Fire wall to reach exit stairway “ST-4” and the second required exit is located on two adjacent “building” for exit stairway “ST-3”. Please provide justification for using Fire Walls as a separate “building” for certain Code provisions, but a single “building” is assumed in means of egress system. Sheet G2.1 Under the “Frontage-Calculations” Tables, revise the numbers on “Aa”. “Aa” is the allowable floor area per story. The number shows on the table is the allowable floor area for the building. Under the “Frontage-Calculations” Tables, Provide tabulation for “Total allowable area” per building. Under the “Frontage-Calculations – Area 1” Table, building perimeter “F” appears to be miscalculated. Open space of East side of the building is only 10 feet, and open space on North side of the building is only 14’. The minimum qualified open space is 20 foot. The “Area increase frontage factor, (If)” should be substantially lower than the calculated value (If) = 62.47%. This calculation affects the maximum allowable area for the story and the building. Please verify calculations for each “building” to ensure the actual floor-area does not exceed the maximum allowable area per each building. SHEET A6.1- Legend references 3 hour firewall on sheet AD1.8 and AD1.9. However, sheet AD1.8 and AD1.9 is missing. This building is of Type III-A construction, provide /show: Continuous drywall behind all tubs is required unless the walls are within the unit and non- bearing. Back to back tubs with a common plumbing wall are impractical in 1-hour buildings. All interior bearing walls shall be constructed of notless than 1-hour fire-resistive construction. (T-601) Attic access openings in 1-hour ceiling can be 2layers of 3/4" plywood or one layer of 1-5/8" T&Gmaterial, self-closing. All openings in floors are required to be enclosed bya shaft having wall, floor, and ceiling of ______2____hour fire resistive construction. (713.1) Recessed ceiling light fixtures must be boxed aroundwith 5/8" Type “X” drywall” to maintain the 1-hourceiling assembly. Continuous drywall is required behind all electricalservice panels, fire hoses and medicine cabinets. Exhaust fans from the bathroom must enter throughthe wall. Dampers are required if the ceiling ispenetrated (717.5) Plumbing penetration through horizontal occupancyseparations shall be boxed out and filled with approved safing material. Insulation is not approved. Penetration of the 1 hour ceiling by ducts from the FAU and the stove hood require dampers (use a ductless hood whenever possible). Attic units (including heat pumps) require dampers at all ceiling penetrations. (711) Steel beams and columns shall be protected asrequired for 1-hour protection. Where ceiling formsthe protective membrane for fire-resistiveassemblies (occupancy separations and rated roof/ceiling or floor/ceiling assemblies), theconstruction (floor joists) and their supportinghorizontal structural members (beams) need not beindividually fire protected except where such members support directly applied loads from morethan one floor or roof. The required fire resistanceshall not be less than that required for individualprotection of members. (704.3) All plumbing penetrations thru walls which requireprotected openings (Fire walls, Fire barriers, Firepartitions) are required to be galvanized or cast ironpiping. FIRE PROTECTIONPlans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Section 106.1.1 and CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana. EXIT ACCESSEXIT ACCESS. That portion of a means of egress system that leads from any occupied portion of a building or structure to an exit. CBC Sections 1002 and 1014.Table 1015.1 Spaces With One Means of Egress: OccupancyMaximum Occupant Load A, B, E, F, M, U49 H-1, H-2, H-33 H-4, H-5, I-1, I-3, I-4, R10 S29 Day care maximum occupant load is 10 EXIT DISCHARGECBC Sections 1002 and 1024, EXIT DISCHARGE. That portion of a means of egress system between the termination of an exit and a public way.CBC Section 1024.6, Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. EXIT SIGNSExit illumination and exit sign requirements in accordance with CBC Section 1011 shall be shown on the drawings. Be specific as to the type of exit signs to be installed.CBC Section 1011.1. Provide a directional exit sign at changes in exiting direction.CBC Section 1011, Requires exit signs to be readily visible from any direction of approach. No point shall be more than 100’ from the nearest visible exit sign. Revise the drawings to show compliance.STRUCTURAL COMMENTS Provide a copy of the soil’s report that addresses the site parameters. Plans showing post tension rebar reinforcement need to be must be clearly identified. Where is the tendon information for the PT slabs? It is not clear on the foundation plan where the interior footing is and where double footing is being used. PT slab clacs, please provide a schematic to show where the loads used in the design of the PT slabs are. It seems some of the bearing walls are supported on the slab; make sure the load imposed by such bearing walls is accounted for in the design of the slab. Are there any rebar in the slab other than the PT? Show on foundation plans. Provide dimensions on foundation plan to show the width of the footing. Due to the size of the building, make sure the key plan provided on the right of the sheet depicts the proper portion of the building shown on the plans. Walls on sheet S7.3.1.F, please clarify the L designation. Clarify the input data provided in the calcs, and called out as Mesh input, what is the number at the beginning of the table refers to? By the way the graphs are a little faint and I can’t read the numbers shown on them. On section or on a separate detail show the footings and the walls of building A as it sits adjacent to that of the parking structure. Dimension the gap between the two building and show (unless obvious) if it is adequate to prevent the two buildings from banging on each other in an earthquake. Identify all fire wall on framing plans, and provide a section that shows specifically the framing around the fire wall; both floor framing and roof framing. Please note, the framing plan should be designed and detailed to ensure that if one side of the fire wall collapse, the other side will stay functional to allow the occupant to exit the building. Clarify the framing plan at the corner of buildings with a cantilevered portion; ex corner unit B6.A1 shown on sheet S3.14. Which direction is the framing at the corner? It is difficult to check the structural calcs. of the moment frame since the plans are not coordinated with the calcs. Please identify on calcs. the location of the moment being designed. (For example, you can call out the coordinate of the moment frame on the calcs). On roof framing plan, show the design load for all Girder trusses. Show all chords and drag trusses and the respective design loads. Provide truss calcs. Stair plans on sheet S3.41, what does the number in the square above the framing line refers to? Sheet S3.36 provide coordinate to be able to locate on the floor plan. Post/trimmer schedule, when do you use the posts designated as c1,c2 ,c3? Provide structural calcs, or if it is already on the plans, specify where, for the sizing of the tie down anchors. Specify an ENR/ICC number for the anchors to be used. Provide calcs to justify adequacy of the tie down anchor/ concrete connection. Provide framing details for the store front at the fitness center, show how it is attached to the floor diaphragm.