Loading...
HomeMy WebLinkAbout222313_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10190560 PROJECT ADDRESS: 4 E Hutton Center Dr Unit# 400 PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: I A, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 8/23/2016 INITIAL REVIEW 9/1/2016 EXPIRATION 2/19/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Rosemary Wood 3. TEL: (949)724-8958 FAX: VALUATION:$684,505.00 EMAIL: rwood@saaia.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.Please return marked up set of drawings with corrections.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceSince there is no rated corridor connecting the two stair enclosures on this floor, show compliance with Sections 909.20.1, 909.20.2.2,909.20.2.4 of CBC for a complyingvestibule connecting to each stair enclosure. Reference each fire-resistive assembly to a CBC Chapter 7, Table and Item number: - Vestibule - Stair enclosures - CorridorsWhen corridor walls are required to be of one-hour fire-resistive construction by Section 1018, every interior door opening shall be protected by a tight-fitting smoke-and-draft-control assembly having a fire-protection rating of not less than 20 minutes. Said doors shall not have louvers. Smoke-and-draft-control door assemblies shall be provided with a gasket so installed as to provide a seal where the door meets the stop on both sides and across the top.Provide a directional exit sign at changes in exiting direction.See red marks on sheet A-0.8 of drawingsShow compliance with Section 1008.1.10 for the doors of training rooms. See red marks on sheet A-2.0 of drawings.