PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10191170
PROJECT ADDRESS:
2302 3/4 S Raitt St Unit# WCC01
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
647-5848FAX:714
647-5897
TYPE OF CONSTRUCTION:
N/A
OCCUPANCY CLASSIFICATION(S):
N/A
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/20/2016
INITIAL REVIEW
10/31/2016
EXPIRATION
4/18/2017
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Barbara Saito
3.
TEL:
(909)723-6152
FAX:
VALUATION:$25,000.00
EMAIL:
barbara.saito@vantagcompany.com
FLOOD ZONE:X-0602320259J
APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840).
- Public Works Agency approval (647-5039).
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance.
Provide information on plans about the poles, section and structural properties.
Basic wind speed used in analysis is wrong it is 110 mph.
Clarify the exposure used and justify.
What about the footing. Please note the wind load at such a height will have the most impact on the footing.
Please clarify on plans and calcs the light pole layout. I. e. does it have the lighting right at the top on aboard, or is there a cantilevered arm that supports the light.