HomeMy WebLinkAbout223436_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10190948
PROJECT ADDRESS:
3325 S Harbor Blvd
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
647-5848FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
A-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
9/29/2016
INITIAL REVIEW
10/19/2016
EXPIRATION
3/28/2017
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Patrick Faranal
3.
TEL:
(909)287-7375
FAX:
(909)591-9792
VALUATION:$20,000.00
EMAIL:
pfaranal@nsmc.com
FLOOD ZONE:X-0602320258J
APPLICABLE CODE: 2013CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTSThis review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceSpecify the type of construction of the building on plans.
Either provide a complete structural calcs.and details of the structural system supporting the curved wall, or provide a copy of the approved plans and calcs.to verify its adequacy.
Looking at the calcs done by KSP consulting, the pole to support the signs seems to be designed for 1 kip vertical and 4 kips lateral. Comparing this to the reaction at the nodes, it seems the maximum reactions At nodes N1 and N2 are much higher; same thing for node N3 and N4, please justify.
KSP consulting should review the load imposed by the sign and indicate that they are ok with it. ( a submittal stamp “No Exception Taken” is good enough)