HomeMy WebLinkAbout225897_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10191675 PROJECT ADDRESS: 1441 W Seventeenth St PLAN CHECK ENGINEER: Chehade, NabilTEL:714 647-5848FAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): B, M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/20/2016 INITIAL REVIEW 1/6/2017 EXPIRATION 6/18/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Cheree Naes 3. TEL: (909)471-1895 FAX: (909)467-8917 VALUATION:$393,984.00 EMAIL: cnaes@core-eng.com FLOOD ZONE:X-0602320144J APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuancePlease provide a detail that shows how the ballast block will be inserted in the tray.( No tray is currently shown on plans).The block should be set in a way that it will not be able to slide out, in addition, it should be able to work in group to resist the uplift imposed at the mechanical anchor.Document on plans the weight of the panel with its support structure including the ballast system.In the structural calcs for the dead load analysis please make sure the ballast system is clearly identified in the total weight imposed.Clarify if there are any penetration of the exterior walls and interior walls. For exterior walls, show where and how close is the wall to the property line or an assumed property line. Please make sure if the wall being penetrated is rated, proper details are provided to address the penetration.If there are any penetration of interior walls, please identify if the wall is a fire wall or Occupancy separation wall ( fire barrier).