HomeMy WebLinkAbout224149_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10191200 PROJECT ADDRESS: 6 E Hutton Center Dr Unit# A PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: I A, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 10/25/2016 INITIAL REVIEW 11/10/2016 EXPIRATION 4/23/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Gary Williams 3. TEL: (949)701-4030 FAX: VALUATION:$103,000.00 EMAIL: gwilliams@lpainc.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3corrected sets of plans.(When needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.Structural drawings to be signed by the same engineer of structural calculations (the engineer responsible in charge of the structural design work).CBC Sections A106.1 and A106.3.4.1.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department (OCFA) approval on the corrected/final sets of drawings (714-573-6108)Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceShow location of Screen wall on the site plan for applicable walls. Provide ventilation justification for open parking structural based on Sections 406.5, 406.5.1 through 406.5.11 of 2013 CBC. The proposed Screen wall is reducing the natural ventilation for existing parking structure with natural ventilation. Drawings to show size and location of openings including calculation for justification are required. Show accessible path of travel (Slope and cross slope) from parking structure to office building, including accessible parking, parking stalls, size, signage and when applicable location of truncated dome. Clarify attachment of each 4’-0”x 11’-6” panel to wall. Please clarify if Details 5, 6. And 7 of Sheet A3.01 are applicable to each panel. Provide Shop drawings on each set of drawings and include the “engineer’s acceptance” statement and signature ofthe engineer in responsible charge of structural calculations. Provide special inspection for screen wall, anchor bolts and welding. The engineer in responsible charge of the structural design work shall include in the construction documents the following:- Structural tests and inspections required by CBC Chapter 17.