HomeMy WebLinkAbout224606_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10191327, 28, 29 PROJECT ADDRESS: 5 E Hutton Center Dr Unit# 130 PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: I A, SPK OCCUPANCY CLASSIFICATION(S): A-3, B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 11/9/2016 INITIAL REVIEW 11/17/2016 EXPIRATION 5/8/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Stephanie Fox 3. TEL: (949)788-4004 FAX: VALUATION:$53,100.00 EMAIL: sfox@waremalcolmb.com FLOOD ZONE:X-0602320278J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3 corrected sets of plans.Please return marked up set of drawings with corrections.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceReference Sheet A0.5, provide missing Sheet A04.a. for path of travel. Indicate slope and cross slop of path of travel. Label and note hourly fire rating of: - All existing or new corridors. Existing corridor fire rating including the 20 minute fire rating of doors to be Maintained. - Hallways(When applicable)Reference Sheet A0.5, please remove T-24 accessibility compliance subject to field inspection and replace with added note on the drawings.Reference each fire-resistive assembly to a CBC Chapter 7, Table and Item number: - Walls - Ceilings - CorridorsFor existing fire rated corridor when modification is made, plans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana.Complete all soffit and furred out wall details. Provide complete detailing, including number, type, location of fasteners and how attachment is made to the building structure. Provide on the drawings interior wall and ceiling finish schedule showing compliance with CBC Section 803 and CBC Table 803.5. Interior floor finishes shall show compliance with CBC Section 804.Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not high hazard occupancy and provide a discernible path of egress travel to an exit. CBC Section 1017.5, Corridor continuity. Fire-resistance-rated corridors shall be continuous from the point of entry to an exit, and shall not be interrupted by intervening rooms.Remove seating area number 920 and maintained the corridor as exiting system. Please label fire rated corridor on the drawings and maintain the fire rating of corridor. Corridors shall be fire-resistance rated in accordance with Table 1017.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions. Note on the drawings CBC Section 715 requirements for a pair of doors installed in a one-hour corridor wall. - A labeled assembly having a fire-protection rating of not less than 20 minutes. - Self-closer or automatic-closer actuated by a smoke detector. - Automatic flush bolts, the door leaf having the automatic flush bolts shall have no doorknob or surface- mounted hardware. The unlatching of any leaf shall not require more than one operation. - Full mortise hinges – three minimum. - Tight-fitting clearances and provided with a gasket so installed as to provide a seal where the door meets the stop on both sides and across the top. Clearances for a pair of swinging doors shall be as follows: With a minus 1/16” tolerance – 1/8” along the top, 1/8” along the hinge and latch jambs, 1/8”along the meeting edge of the doors, and ¼” at the bottom of the doors. - An overlapping astragal extending the full height of the doors is required along the meeting edges of the doors. A coordinating device is also required to insure proper closing.”CBC Section 1024.5.1. provide door closer at 180 degree. Doors, when fully opened, shall not reduce the required width by more than 7” in corridor. Doors in any position shall not reduce the required width by more than one-half. Identify doors to have electronic access/Card reader on the drawings including the door schedule. Show compliance with Sections1010.1.9.9 of CBC.Identify new 20 minute fire rated doors located in existing 1 hour rated corridor. CBC Section 715.4. When corridor walls are required to be of one-hour fire-resistive construction by Section 1017, every interior door opening shall be protected by a tight-fitting smoke-and-draft-control assembly having a fire-protection rating of not less than 20 minutes. Viewport in 20-minute rated door limited to 1” in diameter. Said doors shall not have louvers. Show compliance with section CBC Section 715.5.7.2 where existing walls to be modified. Where corridor walls are required to be one-hour fire-resistive construction by Section 1017, windows shall be protected by fixed glazing listed and labeled for a fire-protection rating of at least three-fourths hour in accordance with Section 715.5. The total area of windows in any portion of an interior corridor shall not exceed 25 percent of the area of the corridor wall of the room which it is separating from the corridor.Provide on the drawings a complete door schedule, showing: - Door sizes (CBC Sections 1008.1.1) - Hardware complying with exiting and disabled accessibility requirements - Compliance with limitation of viewport size (CBC Section 715.4.3 Exception 1)The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. Provide dimensions on the drawings for applicable doors.Slider door is permitted when serving occupant load of 10 or less and to be accessible. Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.All building entrances that are accessible to and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterrupted surface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition. Please refer to red markdrawings. Show location of exit signs on reflected ceiling plan and show exit doors. Requires exit signs to be readily visible from any direction of approach. No point shall be more than 100’ from the nearest visible exit sign. Revise the drawings to show compliance. CBC Section 1011.Exit illumination and exit sign requirements in accordance with CBC Section 1011 shall be shown on the drawings. Be specific as to the type of exit signs to be installed.CBC Section 1011.1. Provide a directional exit sign at changes in exiting direction.CBC Section 1006, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.Section 1013.4 of CBC. Tactile exit signs shall be required at the following locations: Show location of each applicable tactile sign on the reflected ceiling or floor plan and reference to Detail 15 of Sheet A0.3 of CBC. - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” - Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be identified by a tactile exit sign with the following words as appropriate:“EXIT STAIR DOWN”“EXIT RAMP DOWN”“EXIT STAIR UP”“EXIT RAMP UP” - Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure, or an exit passageway, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” - Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” - Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.” It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. If applicable please remove notes referring to ADA compliance from drawings. This project is reviewed for compliance with 2013 CBC. Please refer to red marks on the drawings for Counter height and revise drawings to show compliance. Where counter are provided, at least 5 percent, but never less than one, of each type” to be not more than 28 to 34” high.- Provide a minimum 30” x 48” wheelchair clear floor space. - Provide knee space at tables at least 27” high, 30” wide and 19” deep. - Provide height of tables between 28” – 34” from the floor ground.Show high and low drinking fountain on the drawings. Drinking fountains serving the area of new work shall be accessible. CBC Section 11B-602 of CBC. Show elevation for high and low drinking fountains.Show compliance with Section 902 of CBC for proposed bench and for permanent bench show non-compliance material forType 1-A construction. Provide cross Section to floor plan where bench is proposed. Refer to red marks on the drawings and provide enlarge floor plan of rooms 821 and show glazing compliance. Glass shall be firmly supported on all four edges. Show on the drawings how compliance shall be made with CBC Section 2404. For glass not firmly supported on all four edges, design shall be submitted to the building official for approval.Provide on the drawings a complete window schedule showing: Size (Height and width) of each panel including attachment and Type and thickness of glazing (type of safety glazing for hazardous locations noted under CBC Section 2406.3Glass and glazing shall be in accordance with CBC Chapter 24. Note on the drawings all windows and doors having glazing. Indicate the type and thickness of each light of glazing on the drawings.Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3.Note type of safety glazing complying with CBC Section 2406 for glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24” arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60” above the walking surface.Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use. Note on drawings:- Provide mechanical ventilation for each area/room in accordance with the 2013 California Mechanical Code.Note on drawings:- Artificial light. Artificial light shall be provided that is adequate to provide an average illumination of 10’candles (107 lux) over the area of the room at a height of 30”above the floor level. As of January 1, 2014, SB 407 requires non-compliant plumbing fixtures to be replaced by water-conserving plumbing fixtures when a property is undergoing alterations or improvements as defined by the California Building Code and California Green Building Code. These codes define alteration and improvements as any construction to an existing structure which enhances or improves the structure. Construction related to repairs or maintenance of the structure is not considered to be an alteration or improvement. These fixtures must be installed by the time a final inspection is requested for your project. Note on the drawings Indicating the Building permit number for each floor to justify accessibility compliance. Or add existing as built drawings as reference for accessibility compliance. Please review as built drawings with 2013 CBC with July 1st 2015 Supplements.