HomeMy WebLinkAbout222741_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10190694 PROJECT ADDRESS: 1138 E Seventeenth St PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 9/8/2016 INITIAL REVIEW 9/18/2016 EXPIRATION 3/7/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Martin Rodriguez 3. TEL: (949)254-9380 FAX: VALUATION:$36,438.50 EMAIL: Rodrgz@gmail.com FLOOD ZONE:X-0602320163J APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Please return marked up set of drawings with corrections.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2013 California Building Standards Code with local amendments.Clearly indicate the scope of work under this building permit application: - Revise project job description on the building permit application worksheet to reflect the work to be done under the subject building permit application. - Construction drawings must clearly show all work to be done under the subject building permit application. - Delete all notes and details from drawings that are not a part of the work to be done under the subject building permit application. This includes mechanical, plumbing and electrical work that is not specifically required by the Building Code.All persons preparing plans, specifications, and instruments of service for others shall sign those plans, specifications and other instruments of service for others shall sign those plans, specifications and other instruments of service and all contracts therefore. This requirement applies to both exempt and non-exempt projects. Business and Professions Code Chapter 3, Division 3, Section 5536.1(a).Include address and telephone number of the responsible designer, and date of signing of drawings.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceA separate Building Permit Application is required for: - Each building - Each structure - Each sign - Trash enclosure(s) - Fence(s) - Block wall(s) - Light standard(s) - Pedestrian protection - Demolition - Site improvements - Storage Racks - Screen Wall for Proposed EquipmentSheet CSSheet Index indicates “General Notes” sheet 1 & 2. However, General sheets are missing.Show on the plans: - Complete legal description - Assessor’s Parcel Number - Project Address/Suite/Room Numbers; Building Numbers - Occupancy Classification(s) - Type of Construction - Area tabulation justifying floor area(s) of building(s) (CBC Sections 503, 505, 506, 507, and 508 and CBC Table 503) - Fire Sprinkler System (State purpose of sprinkler system, for example, area increase under CBC Section 506.3, required by CBC Section 903 for type of occupancy, etc.) - Number, width, and purpose (cite code section) of yards required - Number and fire-resistive rating of all area separation walls - Number of stories/mezzanines and building height in feetSheet A-2Specify over-all dimensions on the floor plan.Provide structural details for new walls.Provide the following details and specifications for service counter.11B-904.4.2 Forward approach. A portion of the counter surface that is 36 inches long minimum and 34 inches high maximum shall be provided. Knee and toe space complying with Section 11B-306 shall be provided under the counter. A clear floor of ground space complying with Section 11B-305 shall be positioned for a forward approach to the counter. 11B-306 Knee and toe clearance 11B-306.1 General. Where space beneath an element is included as part of clear floor or ground space or turning space, the space shall comply with Section 11B-306. Additional space shall not be prohibited beneath an element but shall not be considered as part of the clear floor or ground space or turning space. 11B-306.2 Toe clearance 11B-306.2.1 General. Space under an element between the finish floor or ground and 9 inches above the finish floor or ground shall be considered toe clearance and shall comply with Section 11B-306.2. 11B-306.2.2Maximum depth. Toe clearance shall extend 25 inches maximum under an element.Exception: Toe clearance shall extend 19 inches maximum under lavatories required to be accessible by Section 11B-213.3.1. 11B-306.2.3Minimum required depth. Where toe clearance is required at an element as part of a clear floor space, the toe clearance shall extend 17 inches minimum under the element. Exceptions: 1. The toe clearance shall extend 19 inches minimum under sinks required to be accessible by Section 11B-212.3. 2. The toe clearance shall extend 19 inches minimum under built-in dining and work surfaces required to be accessible by Section 11B-226.1. 11B-306.2.4Additional clearance. Space extending greater than 6 inches beyond the available knee clearance at 9 inches above the finish floor or ground shall not be considered toe clearance. 11B-306.2.5 Width. Toe clearance shall be 30 inches wide minimum. 11B-306.3 Knee clearance 11B-306.3.1 General. Space under an element between 9 inches and 27 inches above the finish floor or ground shall be considered knee clearance and shall comply with Section 11B-306.3. Exception: At lavatories required to be accessible by Section 11B-213.3.4, space between 9 inches and 29 inches above the finish floor or ground, shall be considered knee clearance. 11B-306.3.2 Maximum depth. Knee clearance shall extend 25 inches maximum under an element at 9 inches above the finish floor or ground. 11B-306.3.3 Minimum required depth. Where knee clearance is required under an element as part of a clear floor space, the knee clearance shall be 11 inches deep minimum at 9 inches above the finish floor or ground, and 8 inches deep minimum at 27 inches above the finish floor or ground. Exceptions: 1. At lavatories required to be accessible by Section 11B-213.3.4, the knee clearance shall be 27 inches high minimum above the finish floor or ground at a depth of 8 inches minimum increasing to 29 inches high minimum above the finish floor or ground at the front edge of a counter with built-in lavatory or at the front edge of a wall-mounted lavatory fixture. 2. At dining and work surfaces required to be accessible by Section 11B-226.1, knee clearance shall extend 19 inches deep minimum at 27 inches above the finish floor or ground. 11B-306.3.4 Clearance reduction. Between 9 inches and 27 inches above the finish floor or ground, the knee clearance shall be permitted to reduce at a rate of 1 inch in depth for each 6 inches in height. Exception: The knee clearance shall not be reduced at built-in dining and work surfaces required to be accessible by Section 11B-226.1. 11B-306.3.5 Width. Knee clearance shall be 30 inches wide minimum.Provide the following details and specifications for toilet room. See sheet A4 for red marks. Water Closets 11B-604.2 Location. The water closet shall be positioned with a wall or partition to the rear and to one side. The centerline of the water closet shall be 17 inches minimum to 18 inches maximum from the side wall or partition, except that the water closet shall be 17 inches minimum and 19 inches maximum from the side wall or partition in the ambulatory accessible toilet compartment specified in Section 11B-604.8.2. Water closets shall be arranged for a left hand or right-hand approach. 11B-604.3.1 Size. Clearance around a water closet shall be 60 inches minimum measured perpendicular from the side wall and 56 inches minimum measured perpendicular from the rear wall. A minimum 60 inches wide and 48 inches deep maneuvering space shall be provided in front of the water closet. 11B-604.4 Seats. The seat height of a water closet above the finish floor shall be 17 inches minimum and 19 inches maximum measured to the top of the seat. Seats shall not be sprung to return to a lifted position. Seats shall be 2 inches high maximum. 11B-604.5.1 Side wall. The side wall grab bar shall be 42 inches long minimum, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall with the front end positioned 24 inches minimum in front of the water closet. 11B-604.5.2 Rear wall. The rear wall grab bar shall be 36 inches long minimum and extend from the centerline of the water closet 12 inches minimum on one side and 24 inches minimum on the other side. 11B-604.7 Dispensers. Toilet paper dispensers shall comply with Section 11B-309.4 and shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be below the grab bar, 19 inches minimum above the finished floor and shall not be located behind grab bars. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. 11B-604.8.1.1.2 Maneuvering space with side-opening door. In a wheelchair accessible compartment with a door located in the side wall or partition, either in-swinging or out-swinging, a minimum 60 inches wide and 60 inches deep maneuvering space shall be provided in front of the water closet. 11B-604.9.5 Flush controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 11B-309.2 and 11B-309.4 and shall be installed 36 inches maximum above the finish floor. Flush controls shall be located on the open side of the water closet except in ambulatory accessible compartments complying with Section 11B-604.8.2. 11B-604.9.6 Dispenser. Toilet paper dispensers shall comply with Section 11B-309.4 and shall be 7 inches minimum and 9 inches maximum in front of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be 14 inches minimum and 19 inches maximum above the finish floor. There shall be a clearance of 1 ½ inches minimum below the grab bar. Dispensers shall not be of a type that controls delivery or that does not allow continuous paper flow. 11B-605.4Flush controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 11B-309 except that the flush control shall be mounted at a maximum height of 44 inches above the finish floor. 11B-606.2Clear Floor Space. A clear floor space complying with Section 11B-305, positioned for a forward approach, and knee and toe clearance complying with Section 11B-306 shall be provided. 11B-606.5 Exposed pipes and surfaces.Water supply and drain pipes under lavatories and sinks shall be insulated or otherwise configured to protect against contact. There shall be no sharp or abrasive surfaces under lavatories and sinks. Lavatories and Sinks 11B-606.6Adjacent side wall or partition.Lavatories, when located adjacent to a side wall or partition, shall be a minimum of 18 inches to the center line of the fixture. 11B-703.7.2.6.3 Unisex toilet and bathing facilities. Unisex toilet and bathing facilities shall be identified by a circle, ¼ inch thick and 12 inches in diameter with a ¼ inch thick triangle with a vertex pointing upward superimposed on the circle and within the 12-inch diameter. The triangle symbol shall contrast with the circle symbol, either light on a dark background or dark on a light background. The circle symbol shall contrast with the door, either light on a dark background or dark on a light background. 11B-609.4 Position of grab bars. Grab bars shall be installed on a horizontal position, 33 inches minimum and 36 inches maximum above the finish floor measured to the top of the gripping surface, except that at water closets for children’s use complying with Section 11B-604.9, grab bars shall be installed in a horizontal position 18 inches minimum and 27 inches maximum above the finish floor measured to the top of the gripping surface. The height of the lower grab bar on the back wall of a bathtub shall comply with Section 11B-607.4.1.1 or 11B-607.4.2.1.