HomeMy WebLinkAbout222895_3_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10190759
PROJECT ADDRESS:
3760 W McFadden Ave Unit# A Bldg# L
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
9/13/2016
INITIAL REVIEW
11/2/2016
EXPIRATION
3/12/2017
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
David Kang
3.
TEL:
(949)533-4117
FAX:
VALUATION:$100,771.00
EMAIL:
dkang@cdiarc.com
FLOOD ZONE:X-0602320256J
APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH
July 1st 2015 SUPPLIMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Provide plan check respond sheet. Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3 corrected sets of plans. Please refer to red marks on the drawings for additional plan check comments.(When needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)County of Orange Health Department approval on the corrected/final set of drawings (667- 3600)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceValuation of proposed project is calculated as $100,771.00. A minimum of 20% of valuation of construction is required to be spent towards providing disabled access in the priority order as noted in CBC Chapter 11-B, Division 2. Revise the drawings to show compliance. Show both existing elements and how they will be upgraded to current standards.Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC 11-B, Division 2.
- An accessible entrance
- An accessible route to the altered area
- Accessible restrooms
- Parking, signage and alarmsIndicate floor area of dining room. Indicate the occupant load based on occupant load factor of 15. Revise drawings and show occupant load signage on the drawings. Posting of occupant load of (78?). Show location of sign on the drawings. Every room or space that is assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Complete toilet room layout and add missing walls. Remove baby changing table from inside of toilet room compartment. . Provide enlarged dimensioned floor plan of each existing toilet room and show compliance with Sections 603 and 604 of 2013 CBC. Please refer to red marks on the drawings. Sanitation facility toilet room floors shall have a smooth, hard, non-absorbent surface such as Portland cement, concrete, ceramic tile or other approved material which extends upward onto the walls at least 6”. Walls within 2’ of the front and sides of urinals and water closets shall be similarly finished to a height of 4’.Panic hardware shall comply with CBC Section 1008.1.9. Panic hardware shall be provided as required by CBC Section(s). Revise door schedule to show compliance including Fire rating and self-closer of doors. Tactile exit signs shall be required at the following locations, and show location of each applicable sign on the drawings exiting or accessibility drawings: Show location of each sign on the on the drawings.
- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”
- Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual
exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”Show accessibility compliance with following code Sections. Please note that General detail/s or notes are not acceptable in lieu of specific details. Please refer to additional red marks on the drawings for required clearances/ dimensions.
- Section 11B-226, dining surfaces and work surfaces
- Section 11B-213, Toilet and bathing facilities
- Section 11B-703, Signage, Communication elements and features.
- Section 11B-904, Check-out aisles and counters.Show minimum of 44” width of accessible route for kitchen area as marked on the drawings.Show/note ventilation requirements on the plans in accordance with the 2013 CBC and California Mechanical Code (CMC) requirements for each type of use.
Note on drawings: Provide mechanical ventilation for each area/room in accordance with the 2013 California Mechanical Code.
Note on drawings: Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use.Show 5% of dining seating to be accessible. Show locations on the drawings. Minimum of One of each Type is required show and identify location of accessible seating in EACH seating arrangement including high counter bar area. Show location and number of accessible seating (5 %, each Type) in compliance with Section 11B-226, 2013 CBC. All dining, banquet, and bar facilities shall be made accessible to persons with disabilities At least 5%, but not less than one of the seating spaces in each functional area to be accessible as follows: drawing/details are required. Provide specific drawing/details to show compliance. Show location of accessible seating of the floor plan/ furniture plans.
- Provide a minimum 30” x 48” wheelchair clear floor space.
- Provide knee space at tables at least 27” high, 30” wide and 19” deep.
- Provide height of tables between 28” – 34” from the floor ground.
- Provide access to accessible seating space(s) by aisles with a minimum of 36” in width.Indicate the top of fixed or built-in counter, tables is between height of to be at 28” to 34” above the finish floor and knee clearance to be a minimum of 27” high, 30” wide, and 19” deep. One of each type of station shall be located at a section of counter that is at least 60” long and no more than 34” high. Show compliance with following items to insure accessibility for existing or new doors: The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edge for interior doors. Please provide dimensioned at door areas to insure required accessibility compliance. Regardless of the occupant load, there shall be a floor or landing on each side of a door. The floor or landing shall be not more than ½” lower than the threshold of the doorway. Change in level between ¼” and ½” shall be beveled with a slope no greater than 1:2. Change in level greater than ½” shall be accomplished by means of a ramp. Provide detailed sections and plan views showing compliance at all doorways requiring accessibility.Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds.When not All building entrances are accessible and usable by persons with disabilities shall be identified with a least one standard sign and with an additional directional signs, as required, to be visible to persons along approaching pedestrian ways.Required the bottom 10” of all doors except automatic and sliding shall have a smooth uninterruptedsurface to allow the door to be opened by a wheelchair footrest without creating a trap or hazardous condition.
Show compliance with Senate Bill 407 (Copy attached) As of January 1, 2014, SB 407 requires non-compliant plumbing fixtures to be replaced by water-conserving plumbing fixtures when a property is undergoing alterations or improvements as defined by the California Building Code and California Green Building Code. These codes define alteration and improvements as any construction to an existing structure which enhances or improves the structure. Construction related to repairs.
At every entrance and at every major junction along or leading to an accessible route of travel, there shall be a sign displaying the international symbol of accessibility. Signs shall indicate the direction to accessible building entrances and facilities and shall comply with the requirements found in CBC. Provide parking space identification in accordance with CBC Section 11B-222 including:
- An additional sign shall also be posted in a conspicuous place at each entrance to off-street parking facilities, or immediately adjacent to and visible from each stall or space. The sign shall not be less than 17” by 22” in size with lettering not less than 1” in height, with clearly and conspicuously states the following:
Unauthorized vehicles parked in designated accessible spaces not displaying distinguishing placards
license plates issued for persons with disabilities may be towed away at owner’s expense. Towed
- Provide assurance on the drawings that existing signage language reflects the paragraph above. Vehicles may be reclaimed by telephoning the Santa Ana Police Department at (714) 245-8665. CVC 22658a.Provide on the drawings a complete window schedule showing:
- Window sizes
- Type and thickness of glazing (type of safety glazing for hazardous locations noted under CBC Section 2406.3Glass and glazing shall be in accordance with CBC Chapter 24. Note on the drawings all windows and doors having glazing. Indicate the type and thickness of each light of glazing on the drawings.Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3.Note type of safety glazing complying with CBC Section 2406 for glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24” arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60” above the walking surface.If applicable provide Shaft construction detail and fire rating including positive attachment to existing roof on the drawings. Provide structural calculations and drawings, stamped and signed by a California licensed architect or registered civil engineer for: (When applicable).
- Storage racks over 8’ high
- New mechanical equipment on roof (note on roof framing plan weight of each existing and new piece of
equipment on the roof)
- New equipment screening on roof
- Structural support of shaft(s) and/or hood(s)
Additional plan check comments may apply to this project.