HomeMy WebLinkAbout227424_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10592119
PROJECT ADDRESS:
818 S Townsend St
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
2/14/2017
INITIAL REVIEW
3/3/2017
EXPIRATION
8/13/2017
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Roy Zargari
3.
TEL:
(714)651-9233
FAX:
VALUATION:$5,000.00
EMAIL:
FLOOD ZONE:X-0602320257J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016 California Building Standards Code with local amendments.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceCBC Section 1015.3 The top of the guards shall not be less than 42” in height.Provide structural calculations and drawings, stamped and signed by a California licensed architect or registered civil engineer for:
- Stairway(s). CBC Sections 1607, 1630a and 1133B.4, and CBC Table 1607.1, Item 36.
- Handrail(s)/guard(s). CBC Sections 1012, 1013, and 1607.7.
- Guard(s). CBC Sections 1013 and 1607.7.Provide detail to show the stringer is attached to the structure.Provide attachment detail for handrail attached to the structure.Show location of the post on the framing plan.Open riser is not in compliance with CBC2016.Please clarify who will, field verify the floor joists conditions, as it is called on the drawings.Please provide Carbon monoxide detector and Smoke detector for all the units.