HomeMy WebLinkAbout227814_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10192202 PROJECT ADDRESS: 1309 S Rosewood Ave PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 2/27/2017 INITIAL REVIEW 3/6/2017 EXPIRATION 8/26/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Ricardo Maciel 3. TEL: (310)713-9350 FAX: VALUATION:$50,000.00 EMAIL: FLOOD ZONE:X-0602320257JAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.The codes edition on the cover sheet shall be updated to 2016 California Codes.Plans shall clearly show the limit of “FIRE DAMAGE” area. And framing plans shall provide new framing for fire damaged area. The floor plan shall call/ and show that new plumbing walls are framed with 2 X 6 studs. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Public Works Agency approval (647-5039). -Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. Provide and show the location of laundry facility for this project in accordance with the California Plumbing Code (CPC). In every sleeping room shall have at least one openable emergency escape and rescue window or door that meeting all of the following: -An openable area of not less than 5.7 square feet (5.0 square feet for ground-floor openings); -A minimum 24 inch clear openable height; -A minimum clear openable width of 20 inches; -A sill height not over 44 inches above the floor. -show compliance for the existing bedroom window adjacent to (E) family room. See red marks on sheet A-1. (3 X 5 window does not meet the CRC Section 310.2.1 requirements). Show location of 20 x 30 inch attic access with 30-inch minimum headroom. The residence shall conform to the State Energy Conservation Standards. Submit forms and calculations for review and blueprint the final forms on the plans. -Signed Energy Efficiency Documents must be printed on the plans. -Also, submit 2 copies of signed Energy Efficiency calculations. -The permit applicant shall be responsible for obtaining an energy plan check from a consultant who is qualified to perform an energy efficiency analysis in accordance with the California Code of Regulations (CCR), Title 24, Part 1 (Administration) and Part 6 (2016 California Energy Code). The plan check consultant must sign documentation certifying that a thorough, competent review has been performed on behalf of the Enforcement Agency. -The energy plan check consultant must sign documentation forms on behalf of the Building Safety Division. -In Energy calculation submitted with for this plan check, please correct the city and climate zone for this project. -Please refer to attached Residential Lighting Design Guide and revise drawings to show compliance.