HomeMy WebLinkAbout229101_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10192595
PROJECT ADDRESS:
2913 N Bristol St
PLAN CHECK ENGINEER:
Chehade, NabilTEL:714
647-5848FAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
4/10/2017
INITIAL REVIEW
4/28/2017
EXPIRATION
10/7/2017
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Vichuda Fuentes
3.
TEL:
(213)864-4674
FAX:
VALUATION: $30,000.00
EMAIL:
glapm@gridalternatives.org
FLOOD ZONE: X-0602320144J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2010 California Residential Code (CRC); 2010 California Building Code (CBC); CMC = 2010 California Mechanical Code; CPC = 2010 California Plumbing Code; CEC = 2010 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
-Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
Specify the type of construction of the building on the plans.
Please comply with the requirements of section 3111 of the California Building code.
Provide notes on plans to show compliance with the marking requirements specified iun section 3111.2
The array needs to be designed so that it is a maximum of 150 ft by 150 ft. dimension array on the plans.
Identify the roof access points on he plans. Roof access points shall be located in areas that do not require the placement of ground ladders over openings; such as windows or doors.
Access points shall be a minimum of 3 feet wide from ridge to hip.
Access points shall be located at structurally strong locations capable of supporting the live load of fire fighters.
Panels shall be located no higher than 3 feet below the ridge.
There shall be a minimum of 6 feet wide clear perimeter around the edges of the roof.
Provide 4 feet designated pathways to ventilation hatches per section 3111.4.3.2.
Identify all skylights and any roof access hatches on the plans.
All pathways shall be shown to support the weight of the fire fighters and their equipment.
This design assumes that the original building is designed for a 20lb per square foot live load. Please note, based on the span of the beams, the live load could have been reduced in the design. Unless the 20lb per foot could be justified, the assumption should be using the lower reducible load when comparing the load of the panels to the supposedly designed load.
13) Please ensure in your design assumption or justification that the weight of the fire fighters at the access points is taken into consideration.