Loading...
HomeMy WebLinkAbout229422_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10192717 PROJECT ADDRESS: 2800 N Main St Unit# 232 PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: II B, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 4/19/2017 INITIAL REVIEW 5/1/2017 EXPIRATION 10/16/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Bruce Marteney 3. TEL: (909)599-7054 FAX: VALUATION:$194,470.00 EMAIL: pod989@verizon.net FLOOD ZONE:X-0602320163J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. A separate sheet for response may be used.Resubmit 3 corrected sets of plans.(When meeting is needed) Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information. Please remove electrical, mechanical and plumbing sheets.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceReference Sheet D-1 and A-1; provide dimensions to show the floor area of space encroaching into mall required width of exiting system. Show 20’-0” (minimum) clear width of exiting. Show location and size of existing columns and Kiosk/s. The 20’-0” must remain clears at all the time. Please contact mall management office to obtain copy of kiosk and column location in front of store. Summit structural calculations for design and justification of new store front for both vertical and lateral loads including complete attachments details. Incorporate the results of structural calculations into drawings prior to recheck. Engineer / architect signing the calculations to sign and stamp portion of drawings relating to structural calcinations. Provide structural calculations and drawings, stamped and signed by a California licensed architect or registered civil engineer for storage racks over 8’ high.Show/note ventilation requirements on the plans in accordance with the CBC and California Mechanical Code (CMC) requirements for each type of use. Note on drawings: - Provide mechanical ventilation for each area/room in accordance with the 2016 California Mechanical Code. Note on drawings: Show/note LIGHTING requirements on the plans in accordance with CBC and California Electrical Code requirements for each type of use.Note type of safety glazing complying with CBC Section 2406 for hazardous locations listed under CBC Section 2406.3. Please refer to red marks on the drawings. Tenant improvements in the Main Place Mall shall show compliance with the following special provisions and CBC Section 402: - CBC Section 106.3. Tenant improvements at 2800 North Main, Main Place Mall, shall show compliance with “Code Analysis and Fire Protection and Life Safety Concept” prepared by Code Consultants Incorporated, dated “Revised February 18, 1986, and February 22, 1990 (1991 Mall Expansion).” - Note on drawings: Duct and smoke removal system modification is not allowed and shall be in compliance with the “Code Analysis and Fire Protection and Life Safety Concept.” - Main Place Mall, other than anchor stores, is of Type IIB fire-sprinklered construction. In accordance with CBC Section 603.1, walls and permanent partitions shall be of noncombustible construction, except that permanent non-bearing partitions may use fire-retardant treated wood (CBC 202) within the assembly. - CBC Sections 402.7.2 and 708. Each tenant space shall be separated from other tenant spaces by a wall having a fire-resistive rating of not less than one hour. The separation wall shall extend from the floor to the underside of the ceiling above.(When applicable) CBC Section 402.12, Security grilles and doors. Horizontal sliding or vertical security grilles or doors, which are part of a required means of egress, shall conform to the following: - They must remain secured in the full open position during the period of occupancy by the general public. - Doors or grilles shall not be brought to the closed position when there are more than 10 persons occupying spaces served by a single exit or 50 persons occupying spaces served by more than one exit. - The doors or grilles shall be openable from within without the use of any special knowledge or effort when the space is occupied. - When two or more exits are required, not more than one half of the exits may be equipped with horizontal sliding or vertical rolling grilles or doors. - Note on Drawings: Post a legible sign at security grill/door closing controls stating “Security grill/door shall remain secured in the full open position during the period of occupancy by the general public.”Please refer to red marks on the drawings for additional plan check comments. Revised drawings to show compliance.