HomeMy WebLinkAbout225996_3_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10191709 PROJECT ADDRESS: 2100 S Fairview St PLAN CHECK ENGINEER: Mazarji, ZacTEL:714 647-5831FAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/21/2016 Type III-B Construction INITIAL REVIEW 2/8/2017 EXPIRATION 6/19/2017 RECHECKS: 1. 3-26-2017 PROJECT APPLICANT CONTACT PERSON: 2. Thomas Nguyen 3. TEL: (714)728-7266 FAX: VALUATION:$8,500.00 EMAIL: Cal663178@yahoo.com FLOOD ZONE:X-0602320258J Re-check: 3-26-2017 Please revise drawings to show that the new parapet construction (All) withis fire retardant wood.Show (Refer to plan check comment number 7 with initial review date f 2-8-17, see below). Change B-2 occupancy as shown on Sheet TS to B occupancy in compliance with 2013 CBC. Complete attached accessibility Form for full compliance and provide a signed copy on the drawings. APPLICABLE CODE: 2013 CALIFORNIA BUILDING CODE (CBC) WITH July 1st 2015 Supplements including CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5831 for an appointment.Please return marked up set of drawings with corrections.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process.- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance of Worker’s Compensation Insurance.Please specify fire retardant wood for wall and new parapet construction including plywood. Revise parapet details to match and show compliance with existing Type III-B construction. Provide dimensions to match structural calculations for detail # A of Sheet A3. Valuation of proposed project is calculated as $8,500.00. A minimum of 20% of valuation of construction is required to be spent towards providing disabled access in the priority order noted below in plan check comment 10. Drawings to show accessibility compliance with Division 2, Chapter 11B of 2013 CBC. Provide drawings to show how each element listed below will be brought to code compliance: - An accessible entrance - An accessible route to the altered area - Accessible restrooms - Parking, signage and alarms