HomeMy WebLinkAbout230239_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10192988 PROJECT ADDRESS: 3644 S Bristol St PLAN CHECK ENGINEER: Chehade, NabilTEL:714 647-5848FAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): M PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/15/2017 INITIAL REVIEW 5/23/2017 EXPIRATION 11/11/2017 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Aaron Holder 3. TEL: (310)947-4331 FAX: VALUATION:$136,420.00 EMAIL: aholder@BurnhamLA.com FLOOD ZONE:X-0602320259J APPLICABLE CODE: 2010 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5848 for an appointment.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039)\ Add a note that a complete plan of fire sprinkler will be submitted to OC fire prior for approval. Show a floor plan of the tenant corridor shown between the tenants. Show size of all new windows, please note the o be done by landlord should either be shown on the plans of what will be done or identified as work to be done under a separate permit. This includes the new wall at the front and the new windows. Provide a fully dimensioned site plan that shows location of all accessible parking. Dimension the clear space in front of the toilets. Number of fixtures to comply with the mechanical code. Provide a door schedule identifying al new and existing doors. Show the clearances required in front of an accessible toilet per section 11B-604.3.1. Provide the furniture in the breakroom so that a clear landing of 36 X60 is in front of the door. Provide an accessible counter height in beak room. Recheck could be done by making an appointment. It is not clear how the accessible parking is arranged and where the truncated domes are located. Please note parking spaces must be located on areas where persons on wheel chairs are not compelled to wheel behind parked vehicles.