Loading...
HomeMy WebLinkAbout231863_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 10193444 ( Revision to permit # 10192530) PROJECT ADDRESS: 1701 3/4 N Main St Unit# WCC01 PLAN CHECK ENGINEER: Heidari, FredTEL:714 647-5862FAX:714 647-5897 TYPE OF CONSTRUCTION: III A OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 7/6/2017 INITIAL REVIEW 7/17/2017 EXPIRATION 1/2/2018 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Chris Doheny 3. TEL: (619)994-8528 FAX: VALUATION: EMAIL: chris.doheny@smartlinkllc.com FLOOD ZONE:X-0602320163J APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2016 California Building Standards Code with local amendments.This is a revision to a permitted plan that was designed by another engineer. Provide a narrative for this proposed revision.The scope and location for this revision is not clear. The details shown on sheet S-3 & S-4 are tied to any plans location.Plan check stopped due to lack of clarity.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance