HomeMy WebLinkAbout236433_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10194919
PROJECT ADDRESS:
200 E Sandpointe Ave
PLAN CHECK ENGINEER:
Heidari, FredTEL:714
647-5862FAX:714
647-5897
TYPE OF CONSTRUCTION:
II A, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
11/28/2017
INITIAL REVIEW
12/4/2017
EXPIRATION
5/27/2018
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Jay Hennessey
3.
TEL:
(949)257-9184
FAX:
VALUATION:$30,000.00
EMAIL:
jay_hennessey@emcorgroup.com
FLOOD ZONE:X-0602320278J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5862 for an appointment.This review does not include mechanical, plumbing, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide full construction details on the drawings and supporting structural calculation to show that new cooling tower will be secured to existing steel framing to transfer all the loads, vertical and lateral loads; from the proposed tower to existing framing. Detail 1 on sheet S-1.1 is not adequate.Also, the structural details which are part of calculation, drawing # 61437-1C;shall be added to these sets of plans for issuance of building permit.Please add a note on the drawings to reads any fire proofing that get damaged due to replacement of this cooling tower will be fixed before this job is final.Provide a list of all special inspections required under CBC Section 1705 on the drawings.