HomeMy WebLinkAbout237121_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
10195155, 56, 57
PROJECT ADDRESS:
2677 N Main St
PLAN CHECK ENGINEER:
Mazarji, ZacTEL:714
647-5831FAX:714
647-5897
TYPE OF CONSTRUCTION:
II A
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/21/2017
INITIAL REVIEW
1/4/2018
EXPIRATION
6/19/2018
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Monica Maloney
3.
TEL:
(949)679-6456
FAX:
VALUATION:$9,000.00
EMAIL:
monica@cdldesigngroup.com
FLOOD ZONE:X-0602320163J
APPLICABLE CODE: 2016 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTSPlease refer to remarks on the drawings for additional plan check comments. Revise drawings to show compliance with 2016 CBC. This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 714-647-5800 for information. Please remove electrical, mechanical and plumbing sheets.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (714-647-5804.) Previously approved plans
should be submitted to expedite the process.
- Public Works Agency approval (714-647-5039)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuance
It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards. City of Santa Ana does not have jurisdiction to enforce ADA compliance and it is the responsibility of designer. Remove notes referring to ADA compliance on the drawings. This project is reviewed for compliance with 2016 CBC.
Sanitation facility toilet room floors shall have a smooth, hard, non-absorbent surface such as Portland cement, concrete, ceramic tile or other approved material which extends upward onto the walls at least 6”. Walls within 2’ of the front and sides of urinals and water closets shall be similarly finished to a height of 4’.
Reference Sheet A-1.7, show compliance with followings:
Please remove pictogram sign on door entry to toilet rooms. The geometric triangle and circle in compliance with 11B-703.7.2.6. Through 11B- 703.7.2.3.4 to remain at height of 58” to 60”.
Provide room identification sign including tactile signage on the wall adjacent to entry door to toilet room and for additional requirement and dimensions see Section 11B-703.4.2. Revise drawings to show compliance.
For room identification signage, show compliance with Section 703.6 pictogram including tactile and visual signage.
The urinal width to be 36” minimum since the depth of partition is more than 24” in length. Figure 11B-305.7.1, 2016 CBC.
Drawings are too light and difficult to read. Please provide liable drawings.